7500P MAG METER STANDARD SWITCH SETTINGS

½" Meter

(1-30 gpm)

Pre Selection Factor

Jumper Position

1 Pulse Per Gallon

1500

D

10 Pulse Per Gallon

1500

D

100 Pulse Per Gallon

0150

D

500 Pulse Per Gallon

0030

D

1 Pulse Per Liter

3965

D

1" Meter

(3-80 gpm)

1 Pulse Per Gallon

6000

D

10 Pulse Per Gallon

0600

D

100 Pulse Per Gallon

0060

D

500 Pulse Per Gallon

0012

D

1 Pulse Per Liter

1585

D

2" Meter

(10-315 gpm)

1 Pulse Per Gallon

0750

C

10 Pulse Per Gallon

0075

C

1 Pulse Per Liter

0075

C

3" Meter

(24-690 gpm)

1 Pulse Per Gallon

0380

B

10 Pulse Per Gallon

0038

B

1 Pulse Per Liter

0038

B

4" Meter

(40-1200 gpm)

1 Pulse Per Gallon

0250

A

10 Pulse Per Gallon

0025

A

1 Pulse Per Liter

0025

A

PRE-SELECTION SWITCHES

On the board diagram on the previous page, note the po-
sition of the (4) "Pre-Selection Rotary Switches." As per
the above chart, these switches are set at the factory per
meter size and general magnitude of pulse output desired.
If a change of resolution (pulse output value) is required,
change the Pre-Selection Switches to above values.

7

Example:
Setting of Pre-
selection Rotary
Switch Settings

3" Meter with
1 pulse/gallon = 0380

1��

0

10��

8

100��

3

1000�

0

JUMPER LOCATION

Please note in the illustration the jumper area. There are
(4) jumper positions designated by A, B, C, and D.

The

jumper must be located in the correct position for the
respective meter size.
The "D" position is for 1/2" and
1" meters. The A, B, and C positions are for 4", 3" and 2"
sizes respectively. See chart above.