6. Loss-of-Signal Preset

This adjustment establishes the position to which the actuator will travel upon a loss of command signal condition To

activate this setting, SW2 must be OFF (Up) To set a position, press and hold the LOS push-button (S5) and turn the

encoder CW into position

7. Auxiliary Limit Switches

LS3 and LS4 can be set to open or close anywhere within the actuator range Adjust the LS3 and LS4 trim pots to the

desired trip points The adjacent red LEDs indicate the status The auxiliary limit switches are not part of the internal

servo control

8. Verify

Verify the settings by running the actuator through its travel range several times

Dip Switch Configuration SW1

Switch

Switch Position

Function

1

On (Down)

Auto

Off (Up)

Manual

2

On (Down)

LOS–Lock in Place

Off (Up)

LOS–Go to Preset

3

On (Down)

4…20 mA, 0…5V DC

Off (Up)

0…10V DC

4

On (Down)

Split Range Enabled

Off (Up)

Split Range Enabled

5

On (Down)

12…20 mA (if enabled)

Off (Up)

4…12 mA (if enabled)

6

On (Down)

Not Used

Off (Up)

EVA-100/200

Setup for units with only 4 dip switches:

Dip Switch Configuration SW1

Switch

Switch Position

Function

1

On (Down)

Auto

Off (Up)

Manual

2

On (Down)

LOS–Lock in Place

Off (Up)

LOS–Go to Preset

3

On (Down)

4…20 mA, 0…5V DC

Off (Up)

0…10V DC

4

On (Down)

12…20 mA (if enabled)

Off (Up)

4…12 mA (if enabled)

User Manual

Page 11

February 2014