Operation, Specifications, Stroke – Badger Meter Research Control Valve User Manual

Page 7: Stroke speeds, Operation 7, Specifications 7, Stroke 7 stroke speeds 7

Advertising
background image

OPERATION

The Model EVA-100/200 consists of a microprocessor-controlled, stepper motor The stepper motor produces torque, which

is transmitted to the output shaft through a non-rotating drive screw This allows the low torque, high speed motor output to

be converted to high thrust for actuator output shaft motion The built-in servo drive amplifier controls the stepper motor’s

speed and direction It also controls actuator end limits, motor torque, deadband and 4-20 mA transmitter

SPECIFICATIONS

Standard Line Voltage

120/240V AC operation, ± 10% (Slide switch selectable)

Frequency

50/60 Hz

Power

120/240V AC operation – 36VA

Signal Inputs

4…20 mA, 0…5V DC, 0…10V DC

Incremental Control Input

(On/Off control)

Two isolated, dry contact closures required

Position Transmitter

4…20 mA isolated, loop-powered with 12…36V DC external power supply

Field Wiring Terminations

Plugable terminal block, wire size range 26…14 AWG

Loss-of-Signal

Fail to Zero, Span or Lock Last (user-selectable)

Adjustable Limit Switches

4 available, open transistor low level logic outputs, adjustable over stroke

range Rating: 40V DC at 40 mA maximum

Weight

16 lb (7 3 kg)

Conduit Entry

Two 1/2 NPT

Temperature Limits

– 40…150° F (– 40…65° C)

Enclosure

Explosion-proof for Class I, Division 1, Groups C & D Type 4 (IP65), indoor or

outdoor (Vertical mounting only on outdoor installations)

Position Accuracy

1% of full range

Deadband

Factory preset to 1%, field adjustable

Stroke

1 inch (25 4 mm) maximum

Ratings

NEMA 4: Watertight

Explosion-proof: Class 1, Division 1, Group C & D

Standard models approved by CSA

Thrust: 200 lb at minimum step rate for EVA-200

Thrust: 100 lb at minimum step rate for EVA-100

Stroke

Model

Sizes

Stroke

RCV

1/4 in

0 438 in

RCV

1/2 in , 3/4 in , 1 in

0 562 in

9000

ALL

0 750 in

9100

1/2 in , 3/4 in , 1 in

0 750 in

9100

1-1/4 in , 1-1/2 in , 2 in

1 000 in

Stroke Speeds

Thrust

(lb)

Speed

(in./s)

0.438 0.562 0.75

1

Valve Stroke

(in.)

200

0 13

3 4

4 3

5 8

7 7

Stroke (sec )

150

0 19

2 3

3 0

3 9

5 3

Stroke (sec )

100

0 25

1 8

2 2

3 0

4 0

Stroke (sec )

User Manual

Page 7

February 2014

Advertising