Electrical classification – Badger Meter SRD/SRI Valve Positioners User Manual

Page 12

Advertising
background image

Electrical classification

1) 2)

See Certificate of Conformity EX EVE0107A
Type of protection ATEX “intrinsically safe”

Analog positioner (Basic device)

Type AI 636 . . . . . . . . . . . . . II 2 G EEx ib/ia IIB/IIC T4/T6

Certificate of Conformity. . . . PTB 02 ATEX 2206

For use in hazardous areas in circuits certified as

intrinsically safe with the following maximum values:

Input circuit

U

i

. . . . . . . . . . . . . . . . . . . 30 V

I

i

. . . . . . . . . . . . . . . . . . . 130 mA

P

i

. . . . . . . . . . . . . . . . . . . 0.9 W

Internal inductance L

i

. . . . 25 μH

Internal capacitance C

i

. . . 18.9 nF diff. / 22.7 nF to earth

T6 Ambient temperature . . –40 ... 40 °C (–40 ... 104 °F)

T4 Ambient temperature . . –40 ... 80 °C (–40 ... 176 °F)
The control circuit is safely electrically isolated from ground

and all other circuits.

Additional equipment “Inductive limit switch”

For use in hazardous areas in circuits certified as intrinsi-

cally safe with the following maximum values:

U

max

. . . . . . . . . . . . . . . . . 16 V

I

max

. . . . . . . . . . . . . . . . . . 25 mA

P

max

. . . . . . . . . . . . . . . . . 64 mW

Internal inductance . . . . . . 100 μH

Internal capacitance . . . . . 30 nF

T6 Ambient temperature . . –40 ... 40 °C (–40 ... 104 °F)

T4 Ambient temperature . . –40 ... 80 °C (–40 ... 176 °F)
Permissible temperature class and ambient temperature

dependent on the basic device.

Additional equipment “Position Transmitter”

For use in hazardous areas in circuits certified as intrinsi-

cally safe with the following maximum values:

U

i

= 30 V, I

i

= 130 mA, P

i

= 0.9 W

Internal inductance L

i

. . . . 25 μH

Internal capacitance C

i

. . . 17.2 nF diff. / 21 nF to earth

The control circuit is safely electrically isolated from ground

and all other circuits.

Explosion protection Zone 2

It is recommended to use the positioner with explosion prot-

tection "intrinsically safe" acc. to EN 50020 an EN 50014

(consider temperature class). In the EU these positioner

may be operated in Zone 2 with non-intrinsically safe

circuits if the operating values do not exceed the maximum

reference values. The non intrinsic safe circuits has

additionally fulfill the requirements of EN61010-1 (IEC 1010-1),

protection grade III, overvoltage category I (transient voltage

lower than 40 %).

1) With appropriate order only

2) National requirements must be observed

Explosion protection Zone 20

Certificate of Conformity . . . . . . . . . IBExU08 ATEX 1148

EX II 1D Ex iaD 20 T 100°C –40 °C < T

a

< +80 °C

Electrical Data

Supply circuit in type of protection Intrinsic safety Ex ia or

Ex ib

Ui . . . . . . . . . . . . . . . . . 40 V DC

Ii . . . . . . . . . . . . . . . . . . 150 mA

Pi . . . . . . . . . . . . . . . . . 1000 mW

effective inner capacity Ci. . . 6 nF

effective inner inductivity Li . 5 μH
The supply connections have an inner capacity of max. 11 nF

opposite the ground.
The positioner type SRI990 fulfils the requirements of

explosion protection for the Equipment Group II and

Category 1D in type of protection Intrinsic safety for dust

with a maximum surface temperature of 100 °C.

With Electrical Classification ATEX + Zone 20 Dust, Codes

ED4 and EDA, the Travel indicator is not visible.

Type of protection

FM approved for “non-incendive”

Class I, II, III, Division 1, Groups A, B, C, D / T4,

hazardous locations, indoors and outdoors, NEMA 4X

FM approved for “intrinsic safety”

Class I, Division 1, Groups A, B, C, D, E, F, G / T4,

hazardous locations, indoors and outdoors, NEMA 4X

Functional Specifications Common to All Versions

Page 12