Inductive limit switch, Mechanical switches – Badger Meter SRD/SRI Valve Positioners User Manual

Page 14

Advertising
background image

Inductive Limit Switch (

Code T, U

)

Output . . . . . . . . . . . . . . . . . 2 inductive proximity sensors

acc. to DIN 19 234 or NAMUR for connection to

switching amplifier

1)

Current consumption

vane clear . . . . . . . . . . . . > 2.2 mA

vane interposed . . . . . . . . < 1 mA

for control circuit with the following electrical values:

supply voltage . . . . . . . . . DC 8 V, R

i

approx. 1 kOhm

supply voltage range. . . . DC 5 ... 25 V

(with "no Ex")

residual ripple. . . . . . . . . . < 10 % p.p.

permissible

line resistance . . . . . . . . . < 100 Ohms

Response characteristic

2) 3)

switching differential . . . . . < 1 %

switching point repeatability . . . . . < 0.2 %

Terminals for GW1. . . . . . . . 41+, 42–

GW2 . . . . . . . . 51+, 52–

Electrical Classification ATEX

of versions "T" and "U":

Types of protection and temperature classes as basic device,

see

“Electrical classification.”

Additions for this option, Type AI 638 K, in EC- Certificate of

Conformity PTB 00 ATEX 2128:
Types of protection and temperature classes as basic device.

For use in hazardous areas in circuits certified as intrinsic-

ally safe with the following maximum values:

Ui= 16 V, Ii= 25 mA, Pi= 64 mW

Internal capacitance and inductance: Ci= 30 nF, Li= 100 μH

The electric circuits of "Built-in Limit Switch" are galvanically

separated from all other circuits and from earth.

Inductive Limit Switch, three-wire system

– Code R

Input . . . . . . . . . . . . . . . . . . Stroke / angle from actuator

via positioner feedback lever

Output . . . . . . . . . . . . . . . . . 2 inductive proximity sensors,

three-wire system,

LED indication,

contact, pnp

2) 4)

Supply voltage U

S

. . . . . . . . DC 10 ... 30 V

Residual ripple . . . . . . . . . . . ± 10 %, U

s

= 30 V

Switching frequency. . . . . . . 2 kHz

Constant current . . . . . . . . . 100 mA

Response characteristic

6)

Gain . . . . . . . . . . . . . . . . . continuously adjustable

from 1:1 to approx. 7:1

Switching differential . . . . . < 1 %

Switching point

repeatability. . . . . . . . . . . . < 0.2 %

Terminals for GW1. . . . . . . . 42

GW2 . . . . . . . . 52

Supply. . . . . . . 41+, 43-

1) Operating mode min. (= low) / max. (= high)

selectable by adjustment of switch vanes

2) Data measured according to VDI/VDE 2177

3) With stroke 30 mm and lever length 90 mm

Mechanical Switches

(Micro Switches) Code V

(only without Ex protection)

Stroke / angle derived from positioner feedback lever
Output . . . . . . . . . . . . . . . . . 2 mechanical switches (Micro

switches)

5) 6)

Manufacturer . . . . . . . . . . . . Saia-Burgess

Type . . . . . . . . . . . . . . . . . . V4NS-C4-AC1-UL

(UL- and CSA-approved)

Parts set for subsequent mounting:

Code V . . . . . . . . . . . . . . . . EW 426 164 066
Absolute limit values

AC

of mechanical switches built into positioner:

Umax. . . . . . . . . . . . . . . . . . 130 V AC

7)

Imax . . . . . . . . . . . . . . . . . . 0.5 A (resistive Load)

7)

Imax . . . . . . . . . . . . . . . . . . 0.03 A (inductive Load)

8)

Absolute limit values

DC

of mechanical switches built into positioner:

9)

Umax. . . . . . . . . . . . . . . . . . 30 V DC

Imax . . . . . . . . . . . . . . . . . . 1 A
Switching Differential:. . . . . . < 2.5 %

Terminals for SW1 . . . . . . . . 41, 42

SW2. . . . . . . . 51, 52

The circuit of the mechanical switches have to be protected

by a suitable fuse. The diameter of the protective conductor

needs to be at least 1.5 mm² / AWG 16.

5) Operating mode min. (=low) / max. (=high) selectable by adjusting the

respective vane

6) Operating mode normally open / normally closed selectable by vane

adjustment

7) Approval according to UL (UL 1054) and CSA (CSA 22.2 No. 55) at

6,000 operations and T = 65 °C / 149 °F

8) Based on EN 61058-1, at 10,000 operations and T = 85 °C / 185 °F

9) General rating at 50,000 operations and T = 85 °C / 185 °F

Functional Specifications Common to All Versions

Page 14

August 2014

POS-UM-00013-EN-02

Advertising