Built-in limit switches – Badger Meter SRD/SRI Valve Positioners User Manual

Page 13

Advertising
background image

Built-in Limit Switches

Stroke / angle derived from positioner feedback
Inductive proximity sensors,

– standard version (SJ2-N) . . . . . . . Code

T

(down to –20°C)

– security version (SJ2-SN) . . . . . . Code

U

– 3-wire (SI2-K08-AP7/ PNP). . . . . Code

R

(no Ex)

– Micro switches . . . . . . . . . . . . . . . Code

V

(no Ex)

(Details see next page)

Entry for remote potentiometer

(for remote mounting main unit)

– Code D

This remote application is used in applications where high

temperatures or vibration are present and can result in

negative influences to the control. It can also be used in

places not easy to reach, to ensure an easier handling of

the unit, or for cylinders with large strokes.

The Positioner unit (Remote unit) is mounted far away from

the valve or cylinder in a safe environment.

The Potentiometer unit is mounted on the valve or cylinder.

This potentiometer unit can be made of a derivative version

of the SRI990 positioner (only potentiometer in the housing)

or of an external potentiometer like a linear potentiometer

for application onto cylinders, for example.
This option is to be used with a potentiometer unit 3 wires

system with ca. 5 kOhm resistance.
If the following requirements are observed, the set-up is

insensitive to electrical disturbances caused by high

electromagnetic fields, EMC and HF-radiation.

Cable Length max.. . . . . . . . 10 m (32 ft)

Cable Specification (not supplied by Foxboro Eckardt):

• 3-wire twisted pair, shielded

• Shield needs to be connected on both ends to the internal

ground

• Shield endings need to be kept very short when connec-

ting to the ground

• A HF cable gland is not required

For more information about remote mounting please

consult TI EVE0105 R.

Parts Kits for additional installation of auxiliary functions

ti

K

s

tr

a

P

y

l

p

p

u

S

e

d

o

c

l

e

d

o

M
Code T: Limit signal switch, normal version

external

EW 426 164 012

Code U: Limit signal switch, security version

external

EW 426 164 021

Code R: Limit signal switch, 3-wire

external

EW 426 164 057

Code V: Limit signal switch, micro switches

external

EW 426 164 066

Code D: Entry for remote potentiometer

internal

EW 426 164 093

Functional Specifications Common to All Versions

Page 13

August 2014

POS-UM-00013-EN-02

Advertising