Dwyer SCD-LED User Manual

Scd accessory: scd-led instruction sheet

Advertising
background image

SCD Accessory: SCD-LED

Instruction Sheet

Thank you very much for choosing SCD-LED. Please read this instruction sheet before using your SCD-LED to ensure
proper operation. Keep this instruction sheet handy for quick reference.

1

Precaution

1. Please hold the plastic terminal when installing SCD-LED to prevent electrostatic discharge (ESD).
2. Prevent dust or metallic debris from falling into the device and cause malfunction. DO NOT modify

or uninstall SCD-LED without being permitted. DO NOT use empty terminals.

3. When installing SCD-LED, please make sure the power of SCD main unit is switched off and insert

SCD-LED into the correct slot on SCD main unit.

4. Make sure you install SCD-LED correctly before switching on the power; otherwise serious damage

may occur.

5. DO

NOT touch the terminals or repair the device when the power is on; otherwise an electric shock

may occur.

2

Product Outline & Dimension

3

Electrical Specifications

Input power

DC +5V

Power consumption

Max. 0.5W

Display

Single row 7-segment LED display, two 4 bits
PV: red SV: green

Keys

4 keys for selecting, changing pages and tuning

Terminal connection

Can only be inserted into the “Display and Setup Unit” slot on SCD main unit

4

Setting up Parameters

Switching modes: SCD-LED is in ”operation mode” when the power is switched on, Press

to enter

“regulation mode”. Press

for more than 3 seconds in the operation mode to enter “initial setting

mode”. Press

in the regulation mode or initial setting mode to return to the operation mode.

PV/SV: Displaying the present value and set value. Use

to change the set value.

How to set up: Use

in the three modes to select the parameter to be set up and

to

modify the settings. Press

to save the setting.

How to switch modes by keys and set up parameters:

Regulation Mode

Operation Mode

Initial Setting Mode

Select channel


Press

V

Use

to set up target

temperature (SV)

Press

V

Set up input type


Press

V

A

uto-tuning

(Set it up when in PID control and
RUN)

Press

V

Control loop RUN/STOP


Press

V

Set up temperature unit


Press

V

Regulation Mode

Operation Mode

Initial Setting Mode

PID proportional band

(Set it up when in PID control)

Press

V

Set up start pattern

(Set it up when in PID control)

Press

V

Set up upper limit of

temperature

Press

V

Set up PID Ti value

(Set it up when in PID control)


Press

V

Set up start step

(Set it up when in PID program
control)

Press

V

Set up lower limit of

temperature

Press

V

Set up PID Td value

(Set it up when in PID control)

Press

V

Set up the position of

decimal point
(Not for thermocouple R, S, B type)

Press

V

Select control mode



Press

V

or

Set up PD/PID control offset
(When in PID control, set up PdoF
when Ti=0. AT sets up ioF
automatically when Ti≠0.)

Press

V

or

Without/with group INB
Set up upper limit of Alarm 1


Press

V

Set up output 1

(Heating, cooling or proportional
output)


Press

V

Hysteresis for output 1

(Set it up when in ON/OFF control)

Press

V

or

Without/with group INB
Set up lower limit of Alarm 1

Press

V

Set up output 2

(Heating, cooling or alarm output)

Press

V

Hysteresis for output 2

(Set it up when in ON/OFF control)

Press

V

Without group INB

Set up upper limit of Alarm 2

Press

V

or

Without/with group INB
Set up Alarm 1 mode

Press

V

Control cycle for output 1

(Set it up when in PID/programmable
PID/manual control)

Press

V

Without group INB

Set up lower limit of Alarm 2

Press

V

Without group INB

Set up Alarm 2 mode

Press

V

Control cycle for output 2

(Set it up when in PID/programmable
PID/manual control)

Press

V

For locking the keys on the

panel

Press

V

Set up copy function



Press

V

Ratio of output 1 & output 2

when in dual output control.
Pb2 = Pb1 × COEF
(Set it up when in PID/programmable
PID + dual output)

Press

V

For displaying and tuning

the value of output 1
(Displayed when in
PID/programmable PID/manual
control RUN)

Press

V

Select ASCII/RTU communication
format


Press

V

Set up the overlapped area

for dual output (dead band)
(Set it up when in dual output)


Press

V

For displaying and tuning

the value of output 2
(Displayed when in
PID/programmable PID/manual
control RUN)

Press

Z

Return to “target

temperature”

Set up communication

address



Press

V

For tuning temperature

offset

Press

V

Set up communication

baud rate

Press

V

Set up upper limit for

control output

Press

V

Set up data length


Press

V

Set up lower limit for

control output

Press

V

Set up parity bit


Press

V

Regulation Mode

Operation Mode

Initial Setting Mode

Set up delay time for alarm

output

Press

V

Set up stop bit

Press

Z

Return to “set up

input type”

For tuning upper limit of

analog output
(Displayed when in analog output)

Press

V

For tuning lower limit of

analog output
(Displayed when in analog output)

Press

V

Set up positive/negative

proportional output
(Set it up when in proportional output
control)

Press

Z

Return to

“auto-tuning”

5

Types of Input Sensors & Temperature Range

1. Set up input sensor: Enter parameter

(see “Setting up Parameters” section for details) in

“initial setting mode” and select an input sensor (see Table 1).

2. Set up temperature range: Enter parameter

and

(see “Setting up Parameters”

section for details) in “initial setting mode” to set up the temperature range.

3. Set up the position of decimal point: Enter parameter

(see “Setting up Parameters” section

for details) in “operation mode”. The position of decimal point will change the temperature range.
The screen displays only 4 digits; therefore, you have to set “0” in this parameter if you wish to
display values bigger than 999 or smaller than -99. The setting will not be saved. Default = 1.

Input Sensor Type

Display

Range

Platinum resistance (Cu50)

-50 ~ 150°C

Platinum resistance (Ni120)

-80 ~ 300°C

Platinum resistance (Pt100)

-200 ~ 850°C

Platinum resistance (JPt100)

-20 ~ 400°C

Thermocouple TXK type

-200 ~ 800°C

Thermocouple U type

-200 ~ 500°C

Thermocouple L type

-200 ~ 850°C

Thermocouple B type

100 ~ 1,800°C

Thermocouple S type

0 ~ 1,700°C

Thermocouple R type

0 ~ 1,700°C

Thermocouple N type

-200 ~ 1,300°C

Thermocouple E type

0 ~ 600°C

Thermocouple T type

-200 ~ 400°C

Thermocouple J type

-100 ~ 1,200°C

Thermocouple K type

-200 ~ 1,300°C

Table 1

6

Setting up Control Output

For PID Control Application:

1. Set up 2 outputs: Enter parameter

and

in “initial setting mode” (see “Setting up

Parameters” section for details). Set up one of the two parameters as

or

of control

output.

2. Set up control type: Enter parameter

in “initial setting mode” (see “Setting up Parameters”

section for details) and set it up as

(PID) control.

3. Set up parameters: In “regulation mode”

Parameter

Can be set up when parameter

is set as

. When

is set

as

, the program will calculate parameters

,

,

,

and

automatically and save them.

Parameter

,