Operation – Operation Procedures

990-2282A-001

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

11

Parallel System – turning into normal operation from external bypass.

Caution

Never attempt to turn the UPS into normal operation till you have verified that there are no
internal UPS faults.

From the external MBP: Turn all input

switches (

Q001

) to position “1”

(ON)

.

From the external MBP: Check that all the

output lamps

(Q002)

are lit.

From the external MBP: Turn all output

switches

(Q002)

to position “1”

(ON)

. The

lamp indicator of the output isolation breaker

(Q004)

is still lit.

From the UPS: Connect the batteries in the

UPS by pushing them in.

From the XR Enclosure(s) (if available): Set

the DC disconnect switch (if available) to the

ON

position.

From the XR Enclosure(s) (if available):

Connect the batteries by pushing them in.

From the UPS: Turn

ON

all UPS units from

each display via Control–Turn Load ON–

Yes, Turn Load ON.

From the external MBP: Check that all the

lamps (

Q002

) are unlit.

From the UPS: Turn the UPS units into

bypass from one UPS display via Control–

UPS into bypass–Yes, UPS into bypass.

Check that the UPS units are in bypass. The

green (

LOAD ON

) and the yellow (

BYPASS

)

LEDs are lit.

From the external MBP: Check that the lamp

indicator of the output isolation breaker is lit

(

Q004

).

From the external MBP: Turn the output

isolation breaker (

Q004

) to position “1”

(ON)

.

Now the lamps

(Q003 + Q004)

are lit.

From the external MBP: Turn the bypass

switch (

Q003

) to position “0”

(OFF)

. The

lamps (

Q004

) are unlit, but (

Q003

) is lit until

the UPS is running in normal operation.

From the UPS: Turn the UPS units out of

bypass from the display via ControlUPS

out of bypassYes, UPS out of bypass.