Operation – Operation Procedures

18

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

Total power off – isolating one UPS in a parallel system.

Parallel system – turning the isolated UPS into normal operation.

From the UPS: From the Main Menu screen

select Status and scroll down to Status of

actual redundancy: n+ in order to check that

the remaining UPS(s) will be able to carry the

load when one UPS is isolated.

From the UPS: Turn load

OFF

from the display

on the UPS to be isolated via Control–Turn

Load off–Yes, turn Load off.

From the external MBP: Check that the output

lamp

(Q002)

of the UPS to be isolated is lit.

From the external MBP: Turn the output

switch

(Q002)

connected to the UPS you want

to isolate to position “0”

(OFF).

From the external MBP: Turn the input switch

(Q001)

connected to the UPS you want to

isolate to position “0”

(OFF)

.

From the XR Enclosure(s) (if available): Set

the DC disconnect switch (if available) on the

XR Enclosure to the

OFF

position.

From the UPS: Disconnect the batteries in the

UPS which you want to isolate by pulling them

out to the red disconnect line.

From the XR Enclosure(s) (if available):

Disconnect the batteries by pulling them out to

the red disconnect line.

From the external MBP: Turn the input switch

(

Q1)

connected to the UPS you want to turn

into normal operation to position “1”

(ON)

.

From the UPS: Connect the batteries by

pulling them in.

From the XR Enclosure(s) (if available):

Connect the batteries by pulling them in.

From the XR Enclosure(s) (if available): Set

the DC disconnect switch (if available) on the

XR Enclosure to position

ON

.

From the external MBP: Turn the output

switch

(Q002)

connected to the UPS you want

to turn into normal operation to position “I”

(ON).

From the UPS: Turn load

ON

from the display

on the UPS you want to turn into normal

operation via Control–Turn Load on–Yes,

turn Load on.

From the UPS: Press

E

SC

two times to get back

to the Overview Screen.

From the UPS: On the Overview Screen, check

that the load percentage of the UPS units is

approximately the same.