Operation – Operation Procedures

16

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

How to perform a total power off

Total power off – single system without MBP.

Check that the load is

OFF

.

From the UPS: Turn

OFF

the UPS from the

display via Control–Turn Load Off –Yes,

Turn Load Off.

From the XR Enclosure(s) (if available): Set

the DC disconnect switch to the

OFF

position.

From the UPS: Disconnect the batteries by

pulling them out to the red disconnect line

shown on each battery unit.

From the XR Enclosure(s) (if available):

Disconnect the batteries by pulling them out to

the red disconnect line shown on each battery

unit.

Set the utility/mains breaker to the

OFF

or

LOCKED-OUT

position. If the UPS has dual

utility/mains supply, set both supplies to the

OFF

or

LOCKED-OUT

position.

Warning

WARNING!
The lockout procedures at utility/mains breaker must be followed. If necessary, install a
padlock.