Installation Instructions for Innotech Genesis Systems

Edition 011100

2-9

Figure 2-9. DIN Rail Dimensions.

2-3.2.

INSTALLATION GUIDELINES.

To ensure continued reliable operation of

the Genesis II System, the following installation guidelines should be observed:

•

The Genesis II Digital Controller should be installed in a position that provides easy

access to the front panel and sufficient room for power, and input/output cabling. Also,
the Digital Controller should be mounted such that the controls are in easy reach of the
user.

•

Install LEMs as close as possible to the Digital Controller and side-by-side on the DIN

rail. Refer to Paragraph 2-3 and Figure 2-8.

•

Placement of the Genesis II Digital Controller should take into account the optimum

viewing angle of the Liquid Crystal Display (LCD), which is approximately 45

o

vertically

and 90

o

horizontally (see Figure 2-10).

•

Do not mount any unit of the system near high voltage, high current cables or sources of

strong radio frequency emissions such as transmitter antenna cables.

•

The ambient temperature of the Digital Controller and LEMs at the installation site should

not exceed the 0-40ºC temperature range. Ideally, the installation site should have a stable
ambient temperature close to 20

o

C.

•

Mount the units in an area with minimum vibration and minimum exposure to mechanical

damage.

Figure 2-10. Digital Controller Display, Viewing Angles.

ALL DIMENSIONS ARE IN MILLIMETRES

15

35

25

Mounting Slot

18 X 5.2

SIDE VIEW

TOP VIEW

90 DEGREES

45

DEGREES

Advertising