Installation Instructions for Innotech Genesis Systems

Edition 011100

2-12

2-4.3.

ADDITIONAL INSTALLATION GUIDELINES.

For installation of the

Genesis II Digital Controller or GENII MPC system with REMs, observe the applicable
installation guidelines in Paragraph 2-3.2 and the following specific guidelines:

•

Although the Genesis II Digital Controller should be mounted in a location providing easy

access to operating controls and indicators, this requirement does not apply to the Genesis
I Digital Controller and GENII MPC which have no external controls or indicators.

•

Ensure the Digital Controller has been upgraded to Version 4.0 firmware to support the

REMs.

•

Install the GENII RMI on a DIN rail mounting adjacent to the Digital Controller or GENII

MPC. The cable between the RMI and the Digital Controller/MPC must not exceed 1
metre in length.

•

The Digital Controller/MPI can have only one GENII RMI connected to it.

•

Local Expansion Modules cannot be connected to a Digital Controller/MPC that has a

GENII RMI module connected to it.

•

REMs should be mounted in locations such that the cable run between the GENII RMI

and the REMs does not exceed 500 metres in length.

•

REM units should be mounted on DIN rails in cabinets approved for switchgear or

industrial control equipment.

•

Ensure that the types and quantities of REMs assigned to a controller are in accordance

with Paragraph 2-4.1.