NORD Drivesystems BU0270 User Manual

Page 22

Advertising
background image

Supplementary Manual EtherCAT for NORDAC SK 200E

22

Subject to technical amendments

BU 0270 GB

DIP switches

DIP Address

Term.

System bus*

12

11

10

9

8

7

6

5

4

3

2

1

Address

0 0 0 0 0 0 0 0 0 0 0

x

0

0 0 0 0 0 0 0 0 0 0 1

x

1

0 0 0 0 0 0 0 0 0 1 0

x

2

- - - - - - - - - - -

-

-

1 1 1 1 1 1 1 1 1 1 1

x

2047

* x = 0: Termination resistor is not set

x = 1: Termination resistor set


NOTE

Second Address settings are only relevant if the EtherCAT master manages the addresses
of participants via the "Hot Connection Group" functionality.

Termination resistor

EtherCAT: No termination resistors need to be used on the field bus system (EtherCAT)
System bus:

The termination of the BUS system is made at both of its physical ends by connection of
the relevant termination resistors (DIP switches).

 
 
 
 
 
 
 
 
 

e.g.: SK TU4‐ECT 

e.g.: SK 200E 

EtherCAT®- module (View of DIP switch)

SK 200E (internal view)

System bus
termination resistor

System bus

termination resistor


Technology Unit SK TU4-ECT

DIP switch 12-part

Termination of
system bus

Field bus addressing:

2nd Address

Addressing via DIP switches