8 Fault messages

BU 0300 EN

Subject to technical alterations

121

Display

in the ControlBox

Error

text in the Parameter Box

Cause

•

Remedy

Group

Detail in
P700 / P701

E008

8.0

EEPROM parameter loss
(maximum value exceeded) )

Error in EEPROM data

•

Software version of the stored data set not
compatible with the software version of the FI.

NOTE:

Faulty

parameters

are automatically reloaded

(factory setting).

•

EMC interferences (see also E020)

8.1

Invalid inverter type

•

Un-initialised frequency inverter

8.3

EEPROM CIU not recognised

(interface equipment)

EEPROM not present in adapter unit.

•

Switch mains voltage off and on again.

8.4

EEPROM not recognised
internally

EEPROM not present in frequency inverter

• Switch mains voltage off and on again.

8.5

No EEPROM recognised

No EEPROM memory present in system

• Switch mains voltage off and on again.

8.6

Back-up copy used

Internal data used

• Switch mains voltage off and on again.

8.7

Different back-up copy

Internal data overwritten

• Switch mains voltage off and on again.

8.8

Empty EEPROM memory

Un-initialised EEPROM memory

• Switch mains voltage off and on again.

E009

--- ControlBox

error

SPI Bus faulty, no communication with ControlBox.

•

Check ControlBox for correct position.

•

Switch mains voltage off and on again.