Led displays, Io-extension – sk cu4-ioe, Dip switches – NORD Drivesystems TI 275271006 User Manual

Page 4

Advertising
background image

IO-Extension

– SK CU4-IOE

4

TI 275271006 - 4912

DIP switches

Function

DIP-Switch

Meaning

DIP-Switch

Combinations

Assignment

Signal

(DIP-No.)

BIT2

BIT1

BIT0

System bus

termination

resistor

S-Bus Term.
(01)

0
1

not set
setting

Addressing
system bus

S-Bus Adr. Bit 0
(02)

0
0
1
1

0
1
0
1

Adr. 20 (for FI 0 Adr. 32)*
Adr. 21 (for FI 1 Adr. 34)*
Adr. 22 (for FI 2 Adr. 36)*
Adr. 23 (for FI 3 Adr. 38)*

S-Bus Adr. Bit 1
(03)

Analog input

AIN1

Ain1 Mode Bit 0
(04)

0
0
0
1
1

0
0
1
0
0

0
1
0
0
1

0 … 10 V
2 … 10 V
-

10 … 10 V

0 … 20 mA
4 … 20 mA

Ain1 Mode Bit 1
(05)

Ain1 Mode Bit 2
(06)

Analog input

AIN2

Ain2 Mode Bit 0
(07)

0
0
0
1
1

0
0
1
0
0

0
1
0
0
1

0 … 10 V
2 … 10 V
-

10 … 10 V

0 … 20 mA
4 … 20 mA

Ain2 Mode Bit 1
(08)

Ain2 Mode Bit 2
(09)

Analog output

AOUT

Aout Mode Bit 0
(10)

0
0
1
1

0
1
0
1

0 … 10 V
2 … 10 V
0 … 20 mA
4 … 20 mA

Aout Mode Bit 1
(11)

Mode

Second - IOE

2nd IOE Mode
(12)

0
1

First SK-

…-IOE on FI

Second SK-

…-IOE on FI

* With DIP12 = ON: Address 10 … 13 instead of 20 … 23

Pos : 14 /T echnisc he I nf ormati onen/I O - Er weit er ung/ LED Anz eigen [I OE Allgemein] @ 2\ mod_1352390573890_388.doc x @ 51028 @ 6 @ 1

LED Displays

DS

(Device State)

DE

(Device Error)

Meaning
Long flashing

= 0.5 s on / 1 s off

Short flashing

= 0.25 s on / 1 s off

OFF

OFF

Technology unit not ready, no control voltage

ON

OFF

Technology unit ready, no error, at least one frequency inverter is communicating via the system bus

ON

Short flashing

Technology unit ready, however

One or more of the connected frequency inverters is in fault status

Long flashing

OFF

Technology unit ready and at least one further participant is connected to the system bus, but

No frequency inverter on the system bus (or connection interrupted)

Address error for one or more system bus participants

Long flashing

Short flashing

Flash interval

1 x - 1s pause

System bus is in status "Bus Warning"

Communication on system bus interrupted or

No other participant present on the system bus

Long flashing

Short flashing

Flash interval

2 x - 1s pause

System bus is in status "Bus off" or

The system bus 24V power supply was interrupted during operation

Long flashing

Short flashing

Flash interval

3 x - 1s pause

No system bus 24V power supply (system bus is in status "Bus off")

Long flashing

Short flashing

Flash interval

4 x - 1s pause

Module error

EEPROM error

Long flashing

Short flashing

Flash interval

5 x - 1s pause

Module error

AOUT error (analog output)

DIP switch configuration error

OFF

Short flashing

Flash interval

1…7 - 1s pause

System error, internal program sequence interrupted

EMC interference (observe wiring guidelines!)

Module faulty

IO channel

Display

Meaning

IO channel

Display

Meaning

DI 1

ON

High potential DIN1

DO 1

ON

High potential DOUT1

DI 2

ON

High potential DIN2

DO 2

ON

High potential DOUT2

DI 3

ON

High potential DIN3

DI 4

ON

High potential DIN4

DI 3/4, DO 1/2

Available according to the type of IO
module