Error messages, Parameterisation, Further documentation and software (www.nord.com) – NORD Drivesystems TI 275271006 User Manual

Page 5

Advertising
background image

IO-Extension

– SK CU4-IOE

TI 275271006 - 4912

5

Error messages

Error messages for the module - the present or archived messages for the last error - can be read out
via the module parameter (P170) (see Parameterisation).

Error

Meaning

Comments

1000

EEPROM error

EMC fault, module defective

1030

System bus OFF

No 24 V supply to bus, connections not correct

2000

DIP switch changed

DIP switch configuration changed during operation

2001

DIP switch configuration incorrect

Invalid DIP switch settings

2010

Error at analog output

Overload, reference voltage, short-circuit, calibration error

2020

Inverter does not support the module

Incorrect inverter type connected

Pos : 16 /T echnisc he I nf ormati onen/I O - Er weit er ung/ Par ametrierung [I O E Allgemein] @ 2\ mod_1352389903587_388.doc x @ 50978 @ 6 @ 1

Parameterisation

Inverter: In order to establish communication between the inverter and the IOE module, the following
inverter parameters must be changed.

Parameter

Meaning

Comments

(P514)

Bus speed

5 (= 250 kBaud)

(P515 [-01])

Bus address

FI 1 = 32

FI 2 = 34

FI 3 = 36

FI 4 = 38

(P480 [-

01 …-08])

DIN function of the device

Possible settings according to (P420)

(P481 [-

05 …-08])

DOUT function of the device

Possible settings according to (P434)

(P400 [-

03 …-06])

AIN function of the device

Possible settings according to (P400)

(P418 [-

02 …-03])

AUT function of the device

Possible settings according to (P418

IO extension: The module provides a selection of parameters for setting or displaying special
operating values. The parameters can be changed with the aid of the NORDCON software or with a
ParameterBox. Communication is only possible via an SK 54xE or SK 2xxE which is connected to the
module.

Parameter

Meaning

Comments

(P150)

Set relays

Set DOUT directly or control via BUS

(P152)

Factory setting

Reset the module parameters, calibrate AOUT

(P153 [-

01 …-02])

Minimum system bus cycle

Reduction of bus load due to the module

(P160)

Set analog output

Set AOUT directly or control via BUS

(P161 [-

01 …-09])

Filter time

Debounce or round input signals

(P162)

Send broadcast

Activate Broadcast mode (control of several
inverters by this module)

(P163)

Invert analog output

Invert analog signal

(P170 [-

01 … 02])

Present errors

Display of module errors

(P171 [-

01 … 03])

Software version

Firmware version / Revision

(P172)

Configuration

Module type

(P173)

Module status

Status of system bus or connected FI

(P174)

Status of digital inputs

Display of DIN switching status

(P175)

Relay status

Display of DOUT switching status

(P176 [-

01 … 03])

Actual voltage

Voltage level of analog signals

Pos : 17 /T echnisc he I nf ormati onen/I O - Er weit er ung/ Weiterf ührende D okument ati onen und Soft ware [I OE Allgemein] @ 2\ mod_1352390057120_388. doc x @ 51003 @ 6 @ 1

Further documentation and software (

www.nord.com

)

Document

Name

Document

Meaning

NORD CON

Parameterisation and diagnostic software

BU 0200

SK 2xxE frequency inverter manual

BU 0000

Description of NORD CON software

BU 0500

SK 5xxE frequency inverter manual

BU 0040

ParameterBox manual