EtherCAT Bus module – SK CU4-ECT

TI 275271017 - 4913

3

Module features

Parameterisation

Via CoE (CANopen over EtherCat)

Error messages (Emergency Messages)

According to CANopen DS301

EtherCAT addressing (Second Address)

DIP switch or module parameter

Distributed Clocks

Not supported

Access for NORD diagnosis tool via

diagnosis socket on the device (if available) or via the
frequency inverter

Pos : 8 /T ec hnis che Inf or mationen/ SK xU x - Bus - Er wei ter ung en/ Allgemein - Sys temübergreif end/M ont age [ SK CU 4-xxx] @ 3\ mod_1371811235059_388. doc x @ 79455 @ 5 @ 1

Installation

Installation location

Within the connection unit of a frequency inverter (SK 180E, SK 190E, 2xxE)

Mounting

with screw fastenings

Pos : 11 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Allgemei n - Syst emübergreifend/ Ans chl üss e [ SK CU4 - EtherNet Baugruppen allgemein (SK CU 4-EI P / Ansc hlüss e [SK CU 4 - . ..] @ 4\ mod_1378291237620_388. doc x @ 93067 @ 5 @ 1

Connections

Connection is via the terminal bar of the module

Potential

Contact

Designation

Description

1

E

ther

ne

t

E8

PHY1 RX-

Ethernet connection 1 Receive Data -

E7

PHY1 RX+

Ethernet connection 1 Receive Data +

E6

PHY1 TX-

Ethernet connection 1 Transmission Data -

E5

PHY1 TX+

Ethernet connection 1 Transmission Data +

E4

PHY0 RX-

Ethernet connection 2 Receive Data -

E3

PHY0 RX+

Ethernet connection 2 Receive Data +

E2

PHY0 TX-

Ethernet connection 2 Transmission Data -

E1

PHY0 TX+

Ethernet connection 2 Transmission Data +

2

S

y

s

tem

b

us

l

e

v

el

and

di

gi

tal

i

np

ut

s

78

SYS -

System bus data line -

77

SYS +

System bus data line +

C1

DIN1

Digital input 1

C2

DIN2

Digital input 2

40

GND/0V

Reference potential (0 V / GND)

44

24V

Supply voltage (+24 V)

40

GND/0V

Reference potential (0 V / GND)

44

24V

Supply voltage (+24 V)

Schematic diagram - electrical connection

(Terminal designation on example of NORD frequency inverter SK 180E … SK 2xxE)

SK CU4-…

SK 180E … SK 2xxE

VI 24V

GND/0V

SYS +

SYS -

24V

GND/0V

SYS +
SYS -

Pos : 15 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Et herC at/ Konfig urati on [ SK CU4- ECT] @ 3\ mod_1371817147658_388. doc x @ 79506 @ 5 @ 1