Bus signals such as RS485

Data signals for PCs, printers etc.

shielded analog inputs

unshielded direct current (<= 60V)

shielded process signals (<= 25 V)

unshielded alternate current (<= 25V)

coaxial cables for CRT monitors

in common bundles or channels / conduits

direct current from 60 V to 400 V
(unshielded)

alternate current from 25V to 400 V
(unshielded)

in separated bundles or channels /
conduits, without minimum distance

direct and alternate current > 400 V
(unshielded)

Telephone lines

lines leading into EX-rated areas

in separated bundles or channels /
conduits, without minimum distance

Lightning protection


Cabling in areas with a risk of lightning requires a lightning protection. For cabling underground in between
buildings, we recommend the use of special fiber optic cables. If this is not possible, use copper cables that
are suitable for underground installation.

6.2 Guidelines for RS-485 wiring (HF53 with digital option and HF55)


See document E-DV04-RS485.01: RS485 Network Installation and Start-up Guidelines

6.3 Cable grip and cable specifications

The HF5

is supplied either with one M16 sealing cable grip or with a ½” conduit adapter. The M16 cable grip

provides effective sealing only with cables having the proper outside diameter. Preferably, use a cable with an
outside diameter of 6 to 7 mm (0.236 to 0.275 inch) with 18 AWG wires.