TIMER
LIST

‘t i m e r ’’

Name

Scrolling
Display

Parameter Description

Value

Default

Access
Level

T H R E S

TIMER START
THRESHOLD

To set the maximum deviation
between SP and PV before the
timer starts.

Dwell timer and
Programmer only

Off or 1 to 3000 Units above and below setpoint

Off

L3

OFF

Control outputs go to zero %

DwEl

Control continues at SP1

SP2

Go to setpoint 2

E N d . T

TIMER END
TYPE

To determine the action which
takes place when the timer has
timed out.

Dwell timer and
Programmer only

res

Reset programmer

Conf

S S . S P

SOFT START
SETOINT

Sets the threshold below which
the power is limited

SFST timer only

Controller input range

0

Conf

S S . P W R

SOFT START
POWER LIMIT

Sets the limit to the power
output during start up

SFST timer only

0 to 100%

0

Conf

res

Reset

run

Running (counting)

hoLd

Running (hold)

T . S T A T

TIMER
STATUS

Timer status

end

Timed out

L3

Sp

Starts at SP1 (or SP2).

The program must be re-started after a
power failure.

PV

Starts at the current Process value.

The program must be re-started after a
power failure.

sp.rb

Starts at SP1 (or SP2).

The program will continue to run from
the original setpoint value at the last
ramp rate.

s e r v o

SERVO MODE

Defines the way in which the
programmer starts and how it
recovers from a power failure

Programmer only

pv.rb

Starts at the current Process value.

The program will continue to run from
the current process value and ramp back
at the last ramp rate

sp

T s p . 1

TARGET
SETPOINT 1

To set the target value for the
first setpoint

Controller input range

0

L2

R m p . 1

RAMP RATE 1

To set the rate at which the
setpoint changes to reach
TSP.1

Off, 0:1 to 3000 units per min or hour

Off

L2

D w e l . 1

DWELL 1

To set the time at which the
setpoint remains at TSP.1

Off, 0:01 to 99:59 hh:mm or mm.ss

Off

L2

The above three parameters are repeated for the next 3 program segments, i.e. TSP.2, (3 & 4), RMP.2 (3 & 4), DWEL.2 (3 & 4)

d w e l l

SET TIMER
DURATION

To set the time duration (not
programmer)

0:00 to 99:59 hh:mm or mm.ss

0

L3

T . E L A P

ELAPSED
TIME

Time elapsed from when the
timer starts to run

0:00 to 99.59 hh:mm or mm.ss

L3 read
only

T . R E M N

TIME
REMAINING

Time remaining to reach the
set time.

0:00 to 99.59 hh:mm or mm.ss

L3

e v e n t

EVENT
OUTPUTS

Event output operates during
the selected segment

Programmer only

0 = No events operate in any segment

255 -= Events operate in all segments

0 L3

p . c y c l

PROGRAM
CYCLES

Sets the number of times that a
program is repeated

1 to 100

1

L3

c y c l e

PROGRAM
CYCLE

Displays the current cycle
when the program is running

1 to 100

L3

The timer can be restarted from the Reset condition by changing the time remaining parameter.