Appendix a - technical specifications – Sterlco Micro Series Water Temperature Control Unit User Manual

Page 37

Advertising
background image

3200 Series

ACS 3216 Operators Manual 37

11. Appendix A - Technical Specifications

Analogue Input

Sample rate

4Hz (250mS)

Calibration accuracy

+0.25% of reading +1LSD

Resolution

<5, 0.5µV when using a 5 second filter

Linearisation accuracy

<0.1% of reading

Input filter

Off to 59.9 secs

Zero offset

User adjustable over the full display range

Thermocouple Types

Refer to Sensor inputs and display ranges table

Cold junction compensation

Automatic compensation typically >30 to 1 rejection of ambient
temperature change or external reference 0°C (32°F)

CJC Calibration accuracy

<+1.0

o

C at 25

o

C ambient

RTD/PT100 Type

3-wire, Pt100 DIN43760

Bulb current

0.2mA

Lead compensation

No error for 22 ohms in all 3 leads

Process Linear

-10 to 80mV, 0 to 10V with external potential divider module
100K

Ω/800

Current transformer

50mAac into 10 ohm. This burden resistor is fitted inside the controller

Fusing

Fit a 2A type T fuse in line with this controller

Digital input

Contact closure or logic 12V @ 5-
40mA

Contact open >500

Ω

Contact closed <200

Ω

Outputs

Relay

Rating: 2-pin relay

Min: 12V, 100mA dc Max: 2A, 264Vac resistive

Rating: change-over, alarm relay

Min: 12V, 100mA dc Max: 2A, 264Vac resistive

Application Heating,

cooling, alarms or valve position

Logic

Rating

On/High 12Vdc at 5 to 44mA

Application

Off/Low <100mV <100

μA

Heating, cooling, alarms or valve position

Triac

Current at maximum continuous
operation

0.75 A rms (resistive load)

Minimum and maximum operating
voltage

30V rms to 264V rms resistive

Snubber (22nF & 100

Ω)

RC snubber must be fitted externally to prevent false triggering under
line transient conditions

DC analogue output

Rating

0-20mA or 4-20mA software configurable

Maximum load resistance

500

Ω

Isolation

Not isolated from the sensor input

Applications

Heating, cooling or retranmission

Communications

Digital

Transmission standard

EIA-485 2wire or EIA-232 at 1200, 2400, 4800, 9600, 19,200 baud

Protocols Modbus®

SPI ®

Control functions

Control

Modes

PID or PI with overshoot inhibition, PD, PI, P only or On/Off or valve
position

Application

Heating and cooling

Auto/manual Bumpless

transfer

Setpoint rate limit

Off to 9999 degrees or display units per minute

Tuning

One-shot tune

Automatic calculation of PID and overshoot inhibition parameters

Alarms

Types

Full scale high or low. Deviation high, low, or band

Modes

Latching or non-latching. Normal or blocking action

Up to four process alarms can be combined onto a single output

Current Transformer Input