Sterlco Micro Series Water Temperature Control Unit User Manual

Page 38

Advertising
background image

3200

Series

38 ACS 3216 Operators Manual

Input current

0 to 50mA rms calibrated, 50/60Hz

Scale

0 to 10, 25, 50 or 100Amps

Input

impedance

<20

Ω

Accuracy

+4% of reading

Alarms

Leakage current, overcurrent

Indication

Custom scrolling message and beacon

Types

High, low, deviation band, sensor fault, load leakage current, over current,
internal events

Recipes

Number

5

Parameters

stored

38

Selection

Key press or via remote communications

General

Text Messages

10 x 30 character messages

Dimensions and weight

48W x 48H x 90Dmm (1.89W x 1.89H x 3.54D in) 8.82oz (250g)

Power Supply

100 to 240Vac -15%, +10%. 48 to 62Hz. 5 watts max

Temperature and RH

Operating: 32 to 131°F (0 to 55°C), RH: 5 to 90% non-condensing.

Storage temperature

-10 to 70°C (14 to 158°F)

Panel sealing

IP 65, plug-in from front panel

Safety standards

EN61010, installation category II (voltage transients must not exceed
2.5kV), pollution degree 2.

Electromagnetic compatibility

EN61326-1 Suitable for domestic, commercial and light industrial as
well as heavy industrial environments. (Class B emissions, Industrial
Environment immunity).

Low supply voltage versions are suitable for industrial environments
only.

Atmospheres

Not suitable for use above 2000m or in explosive or corrosive
atmospheres.