14 control parameters – TOHO ELECTRONICS TTM-00BT User Manual

Page 14

Advertising
background image

14

Control parameters

a) Identifier

b) Name

c) R/W

d) Description and set range

e) Remark

Initial value (communication
numerical data)
TC, thermocouple;
Pt, resistance bulb

SLH

TC: 01200

Pt: 05000

Set an SV limiter top limit

R/W

R/W of the SV limiter top limit setting
From the bottom limit to the top limit of the set range
Provided that the difference from the SV limiter
bottom limit setting is no less than 50 digits.

For the range, see 7.1
on page 16.

SLL

TC: 0000

Pt: -1000

Set an SV limiter bottom
limit

R/W

R/W of the SV limiter bottom limit setting
From the bottom limit to the top limit of the set range
Provided that the difference from the SV limiter top
limit setting is no less than 50 digits.

For the range, see 7.1
on page 16.

□MD

00001

Set the control mode

R/W

R/W of the control mode setting
00000: Control stop (bottom limit output of the
operation quantity limiter)
00001: Control execution
00002: Manual control

CNT
















00010

Set a control type

R/W

R/W of the control type setting
00①②③

① Function

0

Type A

1

Type B (overshoot inhibition function)

② Output 1 control type

0

None

1

PID control

2

ON/OFF control

③ Output 2 control type (only during heating and

cooling control)

0

None

1

PID control

2

ON/OFF control

Type A:
General and
conventional PID
control

Type B:
Our company's unique
PID control with
reduced overshoot

*4

DIR

00000

Set a forward/reverse
operation switchover

R/W

R/W of the forward/reverse operation switchover
setting
00000: Reverse operation
00001: Forward operation

MV1

00000

Control output 1 operation
quantity

R/W

R/W of the control output 1 operation quantity
Display range: 0.0 to 100.0%
Set range: ML1 to MH1

TUN



00002

Set a tuning type

R/W

R/W of the tuning type setting
00001: Auto-tuning output 1
00002: Self-tuning output 1
00003: Auto-tuning output 2
00004: Self-tuning output 2
00005: Auto-tuning output 1/output 2

ATG

00010

AT factor

R/W

R/W of the AT factor
Set range: 0.1 to 10.0 times

ATC

00020

AT sensitivity

R/W

R/W of the AT sensitivity
Set range: 0 to 999

°

C/0.0 to 999.9

°

C

□P1

00030

Set control output 1,
proportional band

R/W

r/w

R/W of the control output 1, proportional band setting
Set range: 0.1 to 200.0%

□I1

00000

Set an integral time

R/W

r/w

R/W of the integral time setting
Set range: 0 to 3600 seconds

□D1

00000

Set a derivative time

R/W

r/w

R/W of the derivative time setting
Set range: 0 to 3600 seconds

□T1

00020

Set control output 1,
proportional period

R/W

r/w

R/W of the control output 1, proportional period
setting
Set range: 1 to 120 seconds

ARW

01000

Anti-reset windup

R/W

r/w

R/W of the Anti-reset windup
Set range: 0.0 to 100.0%

Advertising