Control parameters

a) Identifier

b) Name

c) R/W

d) Description and set range

e) Remark

Initial value (communication
numerical data)
TC, thermocouple;
Pt, resistance bulb

MH1

01000

Set an operation quantity
limiter, top limit

R/W

r/w

R/W of the operation quantity limiter, top limit setting
Set range: Operation quantity limiter, bottom limit
setting to 100.0%

ML1

00000

Set an operation quantity
limiter, bottom limit

R/W

r/w

R/W of the operation limiter, bottom limit setting
Set range: 0.0 to operation quantity limiter, top limit
setting

□C1

00000

Set a control output 1,
control sensitivity

R/W

r/w

R/W of the control output 1, control sensitivity setting
Set range: 0 to 999

°

C/0.0 to 999.9

°

C

CP1

00000

Control output 1
Set an OFF point

R/W

r/w

R/W of the OFF point setting of control output 1
Set range: -199 to 999

°

C/-199.9 to 999.9

°

C

MV2

00000

Control output 2 operation
quantity

R/W

r/w

R/W of the control output 2 operation quantity
Display range: 0.0 to 100.0%
Set range: ML1 to MH1

□P2

00020

Set control output 2,
proportional band

R/W

r/w

R/W of the control output 2, proportional band setting
Set range: 0.10 to 10.00 times
(Magnification for output 1, proportional band)

□T2

00020

Set control output 2,
proportional period

R/W

r/w

R/W of the control output 2, proportional period
setting
Set range: 1 to 120 seconds

MH2

01000

Set an operation quantity
limiter, top limit

R/W

r/w

R/W of the operation quantity limiter, top limit setting
Set range: Operation quantity limiter, bottom limit
setting to 100.0%

ML2

00000

Set an operation quantity
limiter, bottom limit

R/W

r/w

R/W of the operation limiter, bottom limit setting
Set range: 0.0 to operation quantity limiter, top limit
setting

□C2

00000

Set a control output 2,
control sensitivity

R/W

r/w

R/W of the control output 2, control sensitivity setting
Set range: 0 to 999

°

C/0.0 to 999.9

°

C

CP2

00000

Control output 2
Set an OFF point

R/W

r/w

R/W of the OFF point setting of control output 2
Set range: -199 to 999

°

C/-199.9 to 999.9

°

C

PBB

00000

Manual reset

R/W

r/w

R/W of the manual reset
Set range: 0.0 to 100.0%
But -100.0 to +100.0% during heating/cooling control

□DB

00000

Set a dead band

R/W

r/w

R/W of the dead band
Set range: -100 to 100

°

C/-100.0 to 100.0

°

C

STR

Save data

W

Save data

*1: If the control output 2 control type is ON/OFF control or PID control (if heating/cooling control is conducted), this product cannot be

used as a temperature alarm output.

*2: If the control output 2 control type is used as a temperature alarm output, the monitor for the control output of control output 2 is fixed at

0.

*3: If the control output 2 control type is used as ON/OFF control or as PID control, the temperature alarm output monitor is fixed at 0.
*4: If the control output 2 control type is set to "None": This product produces a temperature alarm output.

For ON/OFF control or PID control: This product performs heating/cooling control.