UEi Test Instruments KM900PLUS User Manual

Page 15

Advertising
background image

KANE900 Plus Operators Manual

Page 14

5.2 Menu Options and Settings

5.2.1 Main Menu


The MAIN MENU consists of 4 sub menus which are shown below and detailed on
the following pages.

MAIN MENU

1.

SELECT 3. DISPLAY

2. UNITS 4. SETUP

All sub-menus are accessed using

and exited using

The

and

keys move the cursor within a menu and allow


parameters to be changed.

TIP Holding down one of these keys scrolls through the data quicker.


5.2.2 Select Menu

F

UEL

O2 Ref
SMOKE
RESET

: NATURAL GAS
:
OFF
:
OFF
:
NO


This menu allows selections to be made for the parameters detailed below.

FUEL :

Select the fuel being used by the boiler from either a standard fuel
stored in the analyser or by entering the user fuel. Once the correct fuel

has been selected press

to view the fuel constants.


NATURAL GAS

K1g
K_2
K_4

: 0.350
: 11.89
: 32

K1n
K_3
O2r

: 0.390
: 9.83
: 3.0


Calculation of fuel constants are detailed in the Appendix. Fuel constants will have to
be calculated before a user fuel can be entered.


Advertising