External connection – APC 60-80kW User Manual

Page 11

Advertising
background image

External Connection

990-4051

Installation Guide APC Silcon 60-80kW 400V UPS

11

* DIN gL types

PVC cables insulated to withstand ambient temperature of max. 30oC
** Must be rated as external PE cable if mains system is not supplying PE

UPS

External

Input

Fuses* FM

[A]

380-415V

External

Input Cable

[mm2]

380-415V

External PE

Cable

[mm2]

Maximum

External

Output
Fuses*

[A]

External

Output

Cable

[mm2]

60kW

125

50

16

100

35

80kW

160

70

35

125

50

NOTICE!

Check correct phase rotation of mains input voltage!!
Max. input/output cables: 120mm

2

.

If there is no neutral input Dzn0 or Dyn11 input isolation transformer is required.

UPS

External Alarm

Cable max.

[mm2]

External System

Earth Cable

[mm2]**

External

Battery Breaker

[A]

External Battery

Cable

[mm2]

60kW

2

25

125

50

80kW

2

25

125

50

NOTICE!

All cable dimensions are recommended sizes only.
Refer to local legal regulations.

NOTICE!

Install gland plate in bottom of unit.

Advertising