Appendix, 0 appendix, 1 table 1. installation planning data – APC 60-80kW User Manual
Page 78

78
Installation Guide APC Silcon 60-80kW 400V UPS
990-4051
Appendix
9.0 Appendix
9.1
Table 1. Installation Planning Data
Main Input
Breaker
Field
Wiring*
Battery Bank**
UPS Module
Service Bypass Panel
Field
Wiring
Output
Breaker
*
** Internal Batteries available for 40kW units and smaller
*
*
Q1
Q2
Q3
* Not supplied by APC
Installation Planning Data
APC Silcon Series
AC Input
Battery System DC
AC Output
Min. Input
Input
Full
I
Nom
I
Max
Load side
Heat
Power rating
Source
P (kW)
I (A)
Cable
Overcurrent
V
n
load
Disch Disch
I
n
Overcurrent Dissipation
kW
kVA
Pf
V
Hz
Nom.
Max.
Nom.
Max.
(per phase)
Protection*
(Vdc)
P(kW)
(A)
(A)
(A)
Protection*
(kW)
60
60
1
380
400
415
50/60
66.1
76.6
105.1
100.5
96.4
115.6
110.6
106.0
50mm
2
125 A
2x384
62.2
81
96
90.9
87.0
83.3
100 A
2.4
80
80
1
380
400
415
50/60
87.9
101.7
139.5
133.5
127.9
153.5
146.8
140.7
70mm
2
160 A
2x384
82.9
108
128
121.2
115.9
111.1
125 A
2.9
COLUMN
1a
1b
1c
1d
1e
1f
1g
1h
2a
2b
2c
2d
3a
3b
4a
NOTES
3
4
1
2
9
5, 6, 13
8
12
10
11
6, 7
13