External Connection

990-4051

Installation Guide APC Silcon 60-80kW 400V UPS

31

4.8.1 Battery Breaker Box

UPS

Ampere

Rating

[A]

Connection

Cable

[mm2]

Max.

short-

circuit

current [kA]

Dimensions

HxWxD [mm]

Weight

[kg]

60 kW
80 kW

125
125

50
50

20
20

540x540x183
504x540x183

20
20