AMX Triple Switch Module 20A RDM-3SWM User Manual

Rdm-3swm, Installation sheet, Triple switch module 20a

Advertising
background image

Installation Sheet

RDM-3SWM

Triple Switch Module 20A

The RDM-3SWM Triple Switch Module is a 20 A triple general purpose
relay module built for compact and economical switching of incandescent
lamps, switched low-voltage transformers, switched fans and electrical
outlets. It is designed for use with the RDA series of enclosures, in an AMX
Lighting™ modular digital dimming system. The RDM-3SWM uses positive
air gap type relays. This module's 120, 240, and 277 VAC ratings are CE,
UL, and C-UL approved.

RDM-3SWM UL and C-UL Ratings (per circuit)

•

General purpose: 2400 W

•

Resistive: 2400 W

•

Ballast: 2400 W

•

Motor: 277 VAC, 1 hp

Suggested Switched Loads

•

Incandescent

•

Low-voltage

•

Motors

•

Switched outlets

•

Fluorescent

Specifications

•

Non-phase dependant

•

Use wires rated at 75°C (167°F)

•

Torque terminals to 7 in-lbs. (0.8 N/M)

•

Max. wire size: 10 AWG (4 mm²)

•

Wire stripping length: 0.28" (7 mm)

•

Weight: 0.95 lbs. (0.43 kg)

•

BTU/hr: 5 each (15 total)

•

Control current: 85 mA per relay (255 mA total) @ 12 VDC

Caution: Pre-Installation Notes

•

All Class 1 wiring must be connected to proper terminals.

•

All control wiring must be connected to proper terminals.

•

Disconnect power while installing or connecting the unit.

•

Keep top and bottom air bents clear at all times.

•

Test loads for shots before connecting.

•

Use low voltage wires with a 300 volt rating or greater.

•

Use field installed copper conductors.

•

All electrical ratings are for continuous duty.

•

For indoor use only.

•

This module may require extra power from the AXlink connection or an

external power supply connected to the control card.

Connecting the RDM-3SWM to the AMX Lighting Master

FIG. 1

RDM-3SWM Triple Switch Module

Relay A

Relay B

Relay C

Line in (hot)

Load out

Mounting
points

Low-voltage control wiring:
4-pin connection to AMX
Lighting master controller

FIG. 2

RDM-3SWM connections

Pin 4 (GND)

Pin 3 (RLY)
Pin 2 (DIM)

Pin 1 (+12 V)

3 (-)

1 (+)

RDM-3SWM 4-pin module connector

4-pin plug from RDM series module

NOTE: The 4-pin plugs from the module connector to
the 4-pin connector on the master (black plug cover facing up).

Advertising