POWER SUPPLY LOCATIONS

Gas Supply:

• The natural gas models are designed to operate at 5”

water column pressure. For proper operation, the

pressure of the natural gas supplied to the regulator

must be between 7” and 13” water column.

• The LP models are designed to operate at 10” water

column pressure. For proper operation, the pressure

of the LP gas supplied to the regulator must be between

11” and 13” water column.

• Locate the pipe stub on the back wall or floor

(see “Product Dimensions and Clearances”). Use 5-foot

maximum length, 5/8” O.D. flexible gas supply line

(3-foot in Massachusetts).

• Install a manual shut-off valve in the gas line

(not provided), in an easily accessible location. Make sure

the homeowner knows where and how to shut off the gas

supply to the rangetop.

Electric Supply:

These rangetops must be supplied with 120 volt, 60 Hz.,

and connected to a dedicated, properly grounded branch

circuit protected by a 15 amp circuit breaker or time

delay fuse.
The power cord of this appliance is equipped with a

three-prong (grounding) plug which mates with a standard

three-prong grounding wall receptacle to minimize the

possibility of shock hazard from this appliance.
If the electrical service provided does not meet the above

specifications, it is recommended that a licensed electrician

install an approved outlet.
DO NOT, UNDER ANY

CIRCUMSTANCES, CUT

OR REMOVE THE THIRD

(GROUND) PRONG FROM

THE POWER CORD.
DO NOT USE AN EXTENSION

CORD WITH THIS APPLIANCE.
• Locate the electric supply

within the area shown or

within reach of the rangetop’s four-foot power cord.

• To avoid tangling cord with items stored in the cabinet,

locate the receptacle on rear wall, inside the cabinet.

7

Installation Preparation

MATERIALS PROVIDED

Regulator

Hold-Down

Strap

TOOLS REQUIRED

Adjustable Wrench

1/4” Driver or

Wrench

Safety Glasses

Drill and

Appropriate Bits

Measuring Tape

Phillips #2

Screwdriver

Saber Saw

Carpenter’s Square

MATERIALS REQUIRED (not provided)

Shut-Off

Valve

Pipe Fittings

5-foot maximum length, 5/8” O.D. CSA-approved

flexible metal gas supply

(3-foot maximum length in Massachusetts only)

NOTE: Purchase new flexible line; do not use

previously used flexible gas line.

Joint

Sealant

Level

Hand Truck