Dc connections, Table 4, Dc conductor size and torque requirements – Outback Power Systems FLEXpower ONE One Fully Pre-Wired Single Inverter System Installation Manual User Manual
Page 29: Figure 13, Ground connections, Installation

Installation
Figure
13
Ground
Connections
DC Connections
Table 4
DC Conductor Size and Torque Requirements
DC Terminal
Minimum Allowed
Conductor Size
Maximum
Conductor Size
Torque
Requirements
Breaker
Size
Battery Positive (+)
2/0 AWG (67.5mm
2
)
N/A (ring terminal)
50 in-lb (5.7 Nm)
175 Adc
Battery Negative (–)
(Shunt)
2/0 AWG (67.5 mm
2
)
N/A (ring terminal)
50 in-lb (5.7 Nm)
N/A
PV Positive (+)
#4 AWG (21.2 mm
2
)
#2 AWG (33.6 mm
2
)
35 in-lb (4 Nm)
80 Adc
PV Negative (–)
#4 AWG (21.2 mm
2
)
#2 AWG (33.6 mm
2
)
35 in-lb (4 Nm)
N/A
Ground Bus Bar
#12 AWG (3.3 mm
2
)
1/0 AWG (53.5 mm
2
)
35 in-lb (4 Nm)
N/A
To make the battery connections in systems that have the FLEXnet DC Monitor, see Figure 14 on
To make the battery connections in systems that do not have the FLEXnet DC Monitor, see Figure
To make the PV connections, see Figure 16 on page 30.
900-0095-01-00 Rev A