Ac connections, Table 5, Ac conductor size and torque requirements – Outback Power Systems FLEXpower ONE One Fully Pre-Wired Single Inverter System Installation Manual User Manual
Page 33: Figure 17, Ac in connections, Installation

Installation
AC Connections
WARNING: Fire Hazard
Multi-wire branch circuits in residential installations can create a potential fire
hazard with inverter installations. Be sure to check for multi-wire branch circuits
before making any AC connections and make any changes required to remove
the hazard.
Table 5
AC Conductor Size and Torque Requirements
AC Terminal
Minimum Allowed
Conductor Size
Maximum
Conductor Size
Torque
Requirements
Breaker
Size
AC IN
#14 AWG (2.1 mm
2
)
1/0 AWG (53.5 mm
2
)
35 in-lb (4 Nm)
60 Aac
AC OUT
#14 AWG (2.1 mm
2
)
1/0 AWG (53.5 mm
2
)
35 in-lb (4 Nm)
60 Aac
Neutral Bus Bar
#14 AWG (2.1 mm
2
)
1/0 AWG (53.5 mm
2
)
35 in-lb (4 Nm)
N/A
Internal components shown may vary from model to model.
Factory wiring is not shown.
See Table 5 for recommended conductor
sizes and torque requirements.
1
See the WARNING on
page 32 for additional
information.
Neutral-to-Ground
Bond
1
Figure 17
AC IN Connections
900-0095-01-00 Rev A
31