Features and specifications – State GPO 69 700OE User Manual

Page 2

Advertising
background image

2

TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION

RELATIVE TO YOUR SAFETY. PLEASE READ THOROUGHLY BEFORE

USING APPLIANCE.

This is a typical oil-fired heater for commercial water heating applications.

The principal components of the heater are shown and identified here.
The identification plate illustrations on page 3 interpret certain markings
into useful information. Use these references to identify the heater and
its components

FEATURES AND SPECIFICATIONS

FIGURE 1.

TABLE 2. RECOVERY CAPACITIES, based on 80% efficiency

TANK

APPROX

U.S Gallons/Hr. and Litres/Hr at TEMPERATURE RISE INDICATED

CAPACITY

EFF.

40F°

50F°

60F°

70F°

80F°

90F°

100F° 110F°

120F° 130F° 140F°

Model

Btuh

KW U.S.Gal. Litres

%

22.2C° 27.7C° 33.3C° 38.8C° 44.4C°

50C° 55.5C° 61.1C° 66.6C° 72.2C° 77.7C°

GPO 199,000 86 80 GPH 477 381 318 272 238 212 191 173 159 147 136

86-199

58 326

LPH 1804 1443 1203 1031 902 802 722 656 601 555 516

GPO 245,000 86 80 GPH 587 469 391 335 293 261 235 213 196 181 168

86-245

72 326

LPH 2221 1777 1481 1269 1111 987 889 808 740 683 635

GPO 315,000 84 80 GPH 754 604 503 431 377 335 302 274 251 232 216

84-315(A)

92 318

LPH 2856 2285 1904 1632 1428 1269 1142 1039 952 879 816

GPO 385,000 75 80 GPH 922 738 615 527 461 410 369 335 307 284 263

75-385(A) 113 284

LPH 3491 2793 2327 1995 1745 1551 1396 1269 1164 1074 997

GPO 455,000 75 80 GPH 1090 872 727 623 545 484 436 396 363 335 311

75-455(A) 133 284

LPH 4125 3300 2750 2357 2063 1833 1650 1500 1375 1269 1179

GPO 700,000 69 80 GPH 1677

1341 1118 958 838 745 671 610 559 516 479

69-700(A) 205 261

LPH 6347 5077 4231 3627 3173 2821 2539 2308 2116 1953 1813

ALL DIMENSIONS IN INCHES/mm

*Model numbers followed by the suffix "A" indicates the optional A.S.M.E. tank construction.

TABLE 1. NOMINAL MODEL DIMENSIONS

GPO 86-199

GPO 86-245

GPO 84-315(A) GPO 75-385(A)

GPO 75-455(A) GPO 69-700(A)

Dim. Inches mm Inches mm Inches mm Inches mm Inches mm Inches mm

A

74 1/2 1,892

74 1/2 1,892

74 1/2 1,892

73 3/4 1,873

73 3/4 1,873

73 3/4

1,873

B

36 3/4 933

36 3/4

933

36 3/4

933

36 3/4

933

36 3/4

933

36 3/4

933

C

27 3/4 705

27 3/4

705

27 3/4

705

27 3/4

705

27 3/4

705

27 3/4

705

D

2 51 2 51 2 51 2 51 2 51 2 51

E

3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT

F

8 203 8 203 8 203 8 203 8 203 10 254

G

26 5/8 676

26 5/8

676

26 5/8

676

24 3/4

629

24 3/4

629

30 3/16

767

H

74 1/2 1,892

74 1/2 1,892

74 1/2 1,892

73 3/4 1,873

73 3/4 1,873

79 3/16

2,011

J 1 1/2 NPT 1 1/2 NPT 1 1/2 NPT 1 1/2 NPT 1 1/2 NPT 1 1/2 NPT

K 1 1/2 NPT 1 1/2 NPT 1 1/2 NPT 1 1/2 NPT 1 1/2 NPT 1 1/2 NPT

L

22 3/4 578

22 3/4

578

22 3/4

578

23 7/16

595

23 7/16

595

28 7/8

733

Approx.

Shipping 553 251 554 252 554 252 624 283 700 318 739 335

Weight STD.

Lbs

Kg.

Lbs.

Kg.

Lbs.

Kg.

Lbs.

Kg.

Lbs.

Kg.

Lbs.

Kg.

Approx.

Shipping

657 298 742 337 747 339 822 373

Weight ASME

---

---

---

---

Lbs.

Kg.

Lbs.

Kg.

Lbs.

Kg.

Lbs.

Kg.

Model

* All tanks are tested at 320 psig working pressure.

** Based on No. 2 fuel oil with a heat content of 140,000 Btu's per gallon at 80% thermal efficiency. Above 2,000 altitude, input

ratings should be reduced 4% for each 1000' above sea level.