Burner installation – State GPO 69 700OE User Manual

Page 8

Advertising
background image

8

A GRAVITY FEED, SUPPLY LINE ONLY, INSTALLATION

FIGURE 10.

If the bottom of the oil tank is at least 2 inches higher than the plug opening at

which the supply line connects to the fuel pump, a single-line gravity-feed system

with 3/8" O.D. tubing may be used with a maximum run length of 100 feet.
• A two stage pump may be used on one line, gravity feed installations.

The pump will function as a single stage unit when the by-pass plug

is not installed.

• Single Stage, Supply and Return Lines. This type of system,

fig. 11, is self-priming. Burner Series No. 940 with by-pass plug field

installed, is for this type of service.

If the tank bottom is no lower than 10 feet below the plug, a single stage

pump may be used but, it must be a two line system with maximum tubing

runs (which includes lift) as shown in Table 6.

A SINGLE STAGE (LOW LIFT), SUPPLY AND RETURN

LINE INSTALLATION - FIGURE 11.

TABLE 6.

Distance Max.

Distance Max.

Tank Run length

Tank Run Length

Bottom Ft. (M)

Bottom Ft. (M)

Below

Below

Pump

3/8" 1/2"

Pump 3/8"

1/2"

Plug

O.D. O.D.

Plug O.D. O.D.

Ft. (M)

Tubing Tubing

Ft. (M)

Tubing

Tubing

1 (0.3)

66 (20.1) 100 (30.4)

6 (1.8)

36 (10.9) 100 (30.4)

2 (0.6)

55 (16.7) 100 (30.4)

7 (2.1)

31 (9.4) 100 (30.4)

3 (0.9)

50 (15.2) 100 (30.4)

8 (2.4)

26 (7.9) 100 (30.4)

4 (1.2)

45 (13.7) 100 (30.4)

9 (2.7)

21 (6.4)

83 (25.2)

5 (1.5)

40 (12.1) 100 (30.4)

10 (3.0)

16 (4.8)

64 (19.5)

Two Stage, Supply and Return Lines: This system, fig. 12, is required when

long lines and high lifts (requiring up to 20" of vacuum and 10' vertical lift) are

encountered. Burner Series No. 941 is used in this service. Bypass plug must

be installed.

A TWO STAGE (HIGH LIFT), SUPPLY AND RETURN

LINE INSTALLATION - FIGURE 12.

If the tank(s) bottom is lower than the plug by more than 10 feet, a two

stage pump with a two line system must be used with maximum tubing

runs (which includes lift) as shown in Table 7.

TABLE 7.

Distance Max.

Distance Max.

Tank Run length

Tank Run Length

Bottom Ft. (M)

Bottom Ft. (M)

Below

Below

Pump

3/8" 1/2"

Pump 3/8"

1/2"

Plug

O.D. O.D.

Plug O.D. O.D.

Ft. (M)

Tubing Tubing

Ft. (M)

Tubing

Tubing

1 (0.3)

74 (22.5) 100 (30.4)

9 (2.7)

51 (15.5) 100 (30.4)

2 (0.6)

71 (21.6) 100 (30.4)

10 (3.0)

48 (14.6) 100 (30.4)

3 (0.9)

69 (21.0) 100 (30.4)

11 (3.3)

45 (13.7) 100 (30.4)

4 (1.2)

66 (20.1) 100 (30.4)

12 (3.6)

42 (12.8) 100 (30.4)

5 (1.5)

63 (19.2) 100 (30.4)

13 (3.9)

39 (11.8) 100 (30.4)

6 (1.8)

60 (18.2) 100 (30.4)

14 (4.2)

37 (11.2) 100 (30.4)

7 (2.1)

57 (17.3) 100 (30.4)

15 (4.5)

34 (10.3) 100 (30.4)

8 (2.4)

54 (16.4) 100 (30.4)

MULTIPLE HEATER FUEL LINES
Where two or more heaters form a water heating system, each burner shall

have an entirely separate oil supply line from the tank to the burner.

BURNER INSTALLATION

GENERAL

An oil Burner Certificate is packed with the oil burner. Following the burner

manual installation the necessary tests shall be performed and the results

recorded on the certificate, see BURNER CERTIFICATE. The certificate and

this instruction manual must be left with the user for future reference. Check

to be certain the heater and burner model numbers are alike and the oil

pump characteristics are proper for the job. See IDENTIFICATION, page 3.

BURNER

The burner assembly is mounted on the flange of the combustion chamber,

fig. 13.

NOTE: Be certain combustion chamber opening is aligned with opening

in heater flange, fig. 13, before placing burner into heater .

1. Place the flange gasket and combustion chamber seal over the burner tube.

2. Place the burner flange on the studs and into the heater flange opening.

ASSEMBLY OF THE OIL BURNER TO THE HEATER

FIGURE 13.

3. Place the flat washers and lock washers over the studs and fasten the

burner in place with the 3/8" - 16 nuts as shown.

Connect the oil line(s) and electrical wires to the burner as follows:
1. The oil pump manufacturer's instructions should be checked for

connection and bleeding information.