15

│

Page

 

 

 

‐Vent clearances‐ 























 

 

Canada

U.S.A 

Direct vent and

other than Direct 

Vent

Direct vent

Other than Direct Vent 

A 

Clearance above grade, veranda, porch, deck, 
or balcony. 

1 foot 

1 foot 

1 foot 

B 

Clearance to window or door that may be 
opened. 

3 feet 

1 foot 

4 feet from below or side 

opening. 1 foot from 

above opening. 

C 

Clearance to permanently closed window

*

*

* 

D 

Vertical clearance to ventilated soffit located 
above the vent terminator within a horizontal 
distance of 2 feet (61cm) from the center line 
of the terminator. 

* 

* 

* 

E 

Clearance to unventilated soffit 

*

*

* 

F 

Clearance to outside corner 

*

*

* 

G 

Clearance to inside corner 

*

*

* 

H 

Clearance to each side of center line extended 
above meter/regulator assembly 

3 feet 

* 

* 

I 

Clearance to service regulator vent outlet.

3 feet

*

* 

J 

Clearance to non‐mechanical air supply inlet 
to building or the combustion air inlet to any 
other application. 

3 feet 

1 foot 

4 feet from below or side 

opening. 1 foot from 

above opening.

K 

Clearance to mechanical air supply inlet.

6 feet

3 feet

3 feet

L 

Clearance above paved sidewalk or paved 
driveway located on public property. 

7 feet 

* 

7 feet 

M 

Clearance under veranda, porch deck, or 
balcony. 

1 foot 

* 

* 

*For clearances not specified in ANSI Z223.1 / NFPA 54 or CAN/CSA‐B149.1, please use clearances in accordance with 
local installation codes and the requirement of the gas supplier. 