Applications 

31

Page

 

 
 
 

In order to purge air in water pipes within a closed‐loop system, an air vent and air 

separator  should  be  installed  in  to  the  system.    Required  circulation  flow  rates  are 
labeled  next  to  each  application  diagram.    These  flow  rate  requirements  must  be 
followed. 

 Toxic  chemicals  used  in  boiler  treatments  such  as  alcohol,  glycerol  and  glycol  groups 

must  not  be  introduced  into  the  system  if  the  system  incorporates  an  open‐loop 
potable water system. 

 The water heater can be used to supply potable water and space heating and shall not 

be connected to any heating system or component(s) previously used with non‐potable 
water where any chemicals were added to the water heating appliances. 

 When  the  system  requires  water  for  space  heating  at  temperatures  higher  than 

required for other uses, a means such as a mixing valve shall be installed to temper the 
water for those other uses in order to reduce scald hazard potential. 

 Water temperature over 125 F (52°C) can cause severe burns instantly or death from 

scalds. 

 Chemicals  such  as  diluted  Glycol  can  be  used  for  radiant  floor,  Hydro/fan  coil  air  or 

Baseboard  heating  only.  The  diluted  solution  of  glycol  must  contain  between  25  and 
55%  of  Glycol.  Be  aware  that  in  closed‐loop  glycol  systems,  low  pressure  in  the  heat 
exchanger can cause low‐temperature boiling, resulting in excessive noise and damage 
to the water heater. Consult with the glycol maker for specifications prior to use.    

APPLICATIONS

 































 












WARNING‐Space‐Heating Applications 

* The recirculation pump is to be controlled by:
‐Dual‐set aquastat (recommended w/timer) 

OR 

‐“Pump Control Connections”. Refer to p24. 
* The recirculation pump is to provide no less 
than 2 GPM and no more than 4 GPM through 
each activated water heater in the system. 

‐Recirculation‐

This is a concept drawing only. 

Check valve

Check valve 

Air 
separator

Recirculation 
pump 

Hot water outlet to fixtures

Air Vent

Unions 

Gas supply 

Ball valves 

Expansion tank 

Y‐Strainer 

Cold water 
inlet 

S