Dip switches of analog output models, Figure 6, Dip switch settings of analog output models – Vaisala HMW90 User Manual

Page 24: On dip, Switches of analog output models

Advertising
background image

User's Guide _______________________________________________________________________

22 ___________________________________________________________________ M211399EN-F

DIP Switches of Analog Output Models

1111-066

Figure 6

DIP Switch Settings of Analog Output Models

DIP Position

Setting

1

Non-metric Non-metric units (°F).

Metric

Metric units (°C).

2

Td

Td (dewpoint) as humidity parameter on display and

analog output. Sets analog output scaling

to -20 ... +55 °C.

RH

RH (relative humidity) as humidity parameter on display

and analog output. Sets analog output scaling to

0 ... 100 %RH.

3

0...5V

0...5V analog output (both channels).

0...10V

0...10V analog output (both channels).

4

Relay On

Relay enabled.

Relay Off

Relay disabled.

5

Relay High Relay closed when measurement above setpoint.

Relay operation is linked to RH on HMW93, and T on

TMW93.

Relay Low Relay closed when measurement below setpoint.

6

Not used

7

Not used

8

Custom

Configuration through service port only.

DIP

Configuration by DIP switches only.

NOTE

DIP switch 2 does nothing on TMW92 and TMW93.

NOTE

If DIP switch 8 is set to Custom, the transmitter ignores all other DIP

switch settings. In custom mode the transmitter uses settings that are

configured in software using the service port.

No

n-M

etr

ic

Td 0..

.5V

Re

lay

On

Re

lay

Hig

h

Cu

sto

m

Me

tric RH

0..

.10

V

Re

lay

Of

f

Re

lay

Lo

w

DI

P

1 2 3 4 5 6 7 8

No

n-M

etr

ic

Td

Cu

sto

m

Me

tric RH

DI

P

1 2 3 4 5 6 7 8

HMW92/TMW92

HMW93/TMW93