Error State

If there are any active “critical” or “error” level errors active in the

transmitter, both analog outputs are set into a defined error level instead

of the measured result. The error level depends on the output type:

- For 0 ... 5 V output, the default error level is 5.5 V
- For 0 ... 10 V output, the default error level is 11 V
- For 4 ... 20 mA output, the default error level is 3.6 mA

If all “critical” and “error” level errors are turned off (by removing their

cause), transmitter resumes normal operation of analog outputs.

You can configure the error level using the AMODE command. See

section Set Analog Output Mode on page 47.

NOTE

You can also use the AOVER command to configure a channel to go to

the error level if the measured parameter is sufficiently far out of the

measured range. See section Set Output Clipping and Error Limit on

page 49.