Wiring hmw95, Connecting several transmitters on same, Rs-485 line (hmw95) – Vaisala HMW90 User Manual

Page 35: Figure 20, Figure 21, Several transmitters on same rs-485 line

Advertising
background image

Chapter 3 ________________________________________________________________ Installation

VAISALA ________________________________________________________________________ 33

Wiring HMW95

The RS-485 line of the transmitter is isolated from the power supply. A

separate ground reference terminal (GND) is provided for the RS-485

connection.

If you are using a shielded cable, you can use the Shld terminal to hold

the exposed part of the shield. Note that the Shld terminal is floating

(not electrically connected).

1209-014

Figure 20

Wiring HMW95

Connecting Several Transmitters on Same RS-485

Line (HMW95)

Set the RS-485 termination jumper to “ON” on the transmitter that is at

the end of the line. This terminates the line with a 120 Ω resistor. For

location of the jumper, see section Transmitter Parts - Inside on page 6.

Connect the cable shield to ground on the building controller side.

1209-015

Figure 21

Several Transmitters on Same RS-485 Line

D-

-Vs

D+

+Vs

+

-

Power supply

18 ... 35 VDC

or 24 VAC ±20%

RS-485

Shld GND

Transmitter

D-

-Vs

D+

+Vs

Shld

GND

Building controller

Transmitter

Transmitter

Power

supply

D-

D+

+Vs

-Vs

GND

SHIELD

RS-485:
BACnet or

MODBUS

master

Connect shield on controller side

Set RS-485

termination jumper

D-

-Vs

D+

+Vs

Shld

GND

D-

-Vs

D+

+Vs

Shld

GND