Troubleshooting guide (cont’d) – Red Lion LEGEND User Manual
Page 49
Advertising
-47-
TROUBLESHOOTING GUIDE (Cont’d)
PROBLEMS
POSSIBLE CAUSE
REMEDIES
INCORRECT RATE READING
1. Input signal type incorrectly selected.
1. Check DIP switches. Set HI/LO FRQ. switch to LO
for a count speed of less than 50 Hz.
2. Inputs improperly connected.
2. Check sensor input connections.
3. Electrical noise interference.
3. Check power source for noise.
a. Check signal wire routing.
4. Scale factor incorrect.
4. Verify scale factor value.
5. Rate input signal too high of a frequency.
5. Verify input signal.
RATE DISPLAY FLASHING OVERFLOW
1. Rate Scale Factor, Multiplier and/or Conversion
Factor values too large.
1. Check values.