APPENDIX “A” - SCALING FOR COUNT INDICATION

The Legend is factory set to provide 1 count on the display for each pulse

that is input to the unit. In many applications, there will not be a one to one
correspondence between input pulses and display units. In these applications
it will be necessary for the Legend to scale or multiply the input pulses by a
scaling factor to achieve the proper display units desired (feet, meters,
gallons, etc.). There are three different parameters used in scaling the input
pulses to the desired reading. They are: the “Count Scale Factor”, the
“Counter Scale Multiplier”, and the “Number of Count Edges”. The number
of count edges is determined in the Program Counter Module. For example,
the number of edges for the “CNT+DIRX1” mode is one and the “QUAD X4”
mode is four. All three are factored together to provide the Total Scaling that
is necessary. The Count Scale Factor and Scale Multiplier are programmed in
the Program Scaling section.

The first step in scaling the counter requires that the “Number of Pulses”

per “Display Unit(s)” needs to be obtained. This may require a small amount
of deductive reasoning.

Example: A 48-tooth gear is mounted to a 2 ft circumference feed roll in a

paper processing plant. It is desired to totalize the total footage of paper
processed. In this example, the display units will be in feet. A sensor sensing
the gear teeth will provide 48 pulses for each revolution of the feed roll. Each
revolution will equate to a linear distance of 2 feet. The number of “Display
Units” desired will be 2. The “Number of Pulses” per “Display Units” will be
48. When the number of “Display Units” and the “Number of Pulses” have
been obtained, the Total Scaling Factor can be calculated.

The “Total Scaling Factor”, denoted as “K

T

”, is simply the total amount of

scaling required. It is obtained by dividing the “Display Units” by the
“Number of Pulses” as shown in Formula #1 below.

FORMULA #1: K

T

= Display Units

¸

Number of Pulses

WHERE:

K

T

= Total Scaling Factor.

Display Units = The number of desired units (revolutions, feet, 10ths of

feet, meters, etc.) that would be acquired after the
“Number of Pulses” has occurred.

Number of Pulses = The Number of pulses required to achieve the number

of “Display Units”.

For the preceding example, the Total Scaling Factor, “K

T

”, is calculated by

plugging in 2 and 48 in the formula:

K

T

= 2

¸

48 = 0.041667

As previously stated, the Total Scaling Factor, “K

T

”, is the combination of

the Scale Factor, Scale Multiplier, and Number of Count edges. In many
applications the Total Scale Factor, “K

T

”, can be programmed directly into

the Count Scale Factor, “SF”, in which case the Scale Multiplier and Number
of Count Edges can be left at the factory settings of X1.

In some applications, more display resolution may be required. When the

Total Scaling Factor (K

T

) is greater than 1.0000 and using only one edge per

count pulse, there may not be enough display resolution.

Example: With a Total Scaling Factor of 2.000, when an input pulse is

generated, the display will increment by 2. If the display units are in feet,
when 3 feet have gone by, the display will still only read 2. It will not
increment again until 4 feet have been accumulated. With this amount of
display resolution it would be impossible to set the Preset and have the output
respond at odd feet intervals (1, 3, 5, etc.). To increase resolution, the Number
of Count edges must be increased. This can be achieved by selecting the
CT+DIRX2 mode (Count plus direction times 2) in the Program Count
Module or by selecting the QUAD X4 mode, if quadrature counting is being
used. If enough resolution still has not been attained, more input pulses will
need to be generated per display unit.

The amount of resolution required will vary depending on the particular

application. In cut-to-length applications, a high amount of resolution is
often necessary. However, in totalizing applications, display resolution may
not be important. It should be noted that whenever the number of count edges
is increased to 2 or 4, the maximum count frequency will decrease. (See
Specifications for maximum count frequency).

Note: When using 2 or 4 edge counting for length sensor, on/off duty cycle

must be 50% to maintain max. accuracy (mag. pickup will not work).