8.0 Troubleshooting

In the event of malfunction or faulty operating performance check that the installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.

-

ATTENTION !
- It is essential that the safety regulations are observed when identifying faults.

If malfunctions cannot be eliminate with the help of the following table

9.0 Troubleshooting table”, the supplier or manufacturer should be consulted.

9.0 Troubleshooting table

ATTENTION !
- read point 10.0 and 11.0
prior to dismantling and repair work!

- read point 6.0 before restarting the plant !

Faults

Possible causes

Corrective measures

Yellow LED is not lit

- Mains failure

- Check power supply

- Incorrect operating voltage

- Connect operating voltage in

accordance with type identification
plate

- Electronic positioner burnt out

- Check whether mains voltage

agrees with the voltage specified
on type identification plate.

Replace electronic positioner.

- Connection terminal not connected

correctly or cable has no contact in
connection terminal

- Firmly plug in connection terminal

and check connection cable

Electronic positioner cannot be
adjusted

- Potentiometer not connected cor-

rectly

- Check connections

- Potentiometer has incorrect value

rating

- Replace potentiometer by

1000

 potentiometer

- Potentiometer connected to incor-

rect terminal

- Correct connection in accordance

with circuit diagram

- Actuating signal not applied

- Connect actuating signal

- Actuating signal connected to

incorrect terminal

- Correct connection in accordance

with circuit diagram

- Adjusting screws N (zero point)

and S (slope span) are out of
range

- Carry out settings as described

under 6.0 to 6.6

- Effective direction switch SW

switched incorrectly

- Switch effective direction switch in

accordance with 6.4

- Switching outputs to motor burnt

out

- Check whether motor or supply

line has a short.Replace elec-
tronic positioner

Advertising