ARI Armaturen ES11 EN User Manual

Page 22

Advertising
background image

Page 2-22

Rev. 0040601000 1014

Operating and installation instructions

Electronic positioner ES11

Outputs swing at short intervals
between clockwise and counter-
clockwise

- Adjusting screws not set in stand-

ard control range

- Carry out settings as described

under 6.0 to 6.6

- Potentiometer not OK.

- Replace potentiometer

- Electromagnetic interference of

actuating signal

- Install filter to actuating signal input

Motor in actuator does not oper-
ate but LEDs are lit

- Electrical connection from elec-

tronic positioner to actuator not
OK.

- Check electrical connections and

terminals

- Electronic positioner outputs are

burnt out

- Check whether motor voltage

agrees with the voltage specified
on the type identification plate.

Check whether the motor or supply
line has a short.

Replace electronic positioner

- Cable connection not OK.

- Check cable connection for correct

wiring and electrical contact.

- Motor burnt out.

- Check whether motor or supply

line has a short.

Replace motor.

Motor in actuator operates in only
one direction

- The positioner switch in the actua-

tor limits the control range

- Check cable connection for correct

wiring and contact

- Cable connection not OK

- Check whether motor or supply

line has a short.

- Only one electronic positioner out-

put burnt out - Adjust position
switch

- Replace electronic positioner.

Actuator does not cover entire
control range

- Spur gear transmission ratio at

potentiometer incorrect

- Adapt spur gear transmission ratio

to control range

- Adjusting screws N (zero point)

and S (slope span) out of range

- Carry out settings as described

under 6.0 to 6.6

Advertising