4 installation in cs25 to cs27 actuator, 4 installation in cs25 to cs27 actuator -7 – ARI Armaturen ES11 EN User Manual

Page 7

Advertising
background image

Rev. 0040601000 1014

Page 2-7

Operating and installation instructions

Electronic positioner ES11

5.4 Installation in CS25 to CS27 actuator

Refer to figure below for installation in CS25 to CS27 actuator.

fig. 3

Installation procedure:
- Carefully remove cover.
- Loosen capacitor, for this purpose, release corresponding cable ties.
- Secure capacitor plate with screw DIN EN ISO 4762 - M8x10 on to gearbox cover.
- Install capacitor on capacitor plate
- Secure mounting bracket on gearbox cover with two self-tapping screws M4x8 DIN 7500.
- Secure ES11 to mounting bracket with two socket head cap screws DIN EN ISO 4762 -

M4x12.

- Connect cable of CS electronic positioner to terminal block and plug into ES11 cable.
- Tie together newly installed cables with cable ties.
- Remove old circuit diagrams from cover and affix new circuit diagram in cover.

ATTENTION !
For potentiometer installation, refer to operating instructions for CS actuators.

Mounting parts:

- 1 Electronic positioner ES11
- 1 Mounting bracket ES11/RI21
- 2 Socket head cap screws DIN EN ISO 4762 - M4x12
- 1 Socket head cap screws DIN EN ISO 4762 - M8x10
- 1 Capacitor plate
- 2 Self-tapping screws DIN 7500 - M4x8
- 1 1000 Ohm potentiometer, soldered
- 2 Lock rings for potentiometer
- 1 Pinion for potentiometer
- 1 CS electronic positioner cable
- 1 Circuit diagram ES11 + CS25
- 2 Cable ties

Advertising