CMOR Dome

Videoswitch Page

2

Vc601i.doc

1.1.4 Termination

• If you are using a star expander (eg. Videoswitch Vi-E2) to drive multiple domes

(which is the recommended method) all domes should be have termination ON.

• If you are using an alarm module, termination in the dome should also always be

ON.

• If you are daisy-chaining domes, for all except the last in the daisy chain, you will

need to turn the termination of the alarm module OFF (if fitted) or else turn the
termination of the dome OFF. The dome at the end of the daisy chain must have its
termination ON and likewise the termination of the alarm module (if fitted) must be
ON.

If you do need to turn the termination of a dome OFF, you will have to either:

• If your CMOR Evolution dome has no DIP switches, the termination is set via its

menu.

• If your CMOR Evolution domes does have DIP switches, set the termination switch

as described in section 1.2.5.

1.2 CMOR Classic Configuration

The CMOR dome is supplied with DIP switches set for the following configuration:

Twisted pair:

Address:

1

Protocol: Videoswitch

VXP4

Baud

rate:

9600

baud,

Termination:

ON

Up-the-coax: BBV

compatible

8-way DIP switch

Dome
Address 1 2 3

4 5 6 7

8

1

1 0 0

0 0 0 0

0

6-way DIP switch

Protocol, baud, termination

1

2

3

4

5

6

VXP4&Coax/9600 baud/On

0 0

0

0

0

1

1.2.1 Removing the DIP switch cover

If you need to change DIP switch settings, you may do so either before or after the dome is
mounted on its bracket, whichever is more convenient.

• Using a large flat bladed screwdriver, unscrew the DIP switch access screw (A) on

the rear of the dome by turning counter-clockwise