Listings and approvals, Specifications – Notifier FSC-851 User Manual

Page 2

Advertising
background image

Page 2 of 2 — DN-60412:B • 08/25/2010

Notifier®, System Sensor®, and FlashScan® are registered trademarks

and

IntelliQuad™ is a trademark of Honeywell International Inc.

©2010 by Honeywell International Inc. All rights reserved. Unauthorized use

of this document is strictly prohibited.

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.

www.notifier.com

B224BI: Isolator base. Dimensions: 6.2" (15.748 cm) x 1.2"

(3.048 cm). Maximum: 25 devices between isolator bases.
B224BIA: Isolator base, ULC Listed.

Listings and Approvals

UL Listed: S911

ULC Listed: S1115 (FSC-851A)

• FM Approved

CSFM: 7272-0028:0255

Specifications

GENERAL SPECIFICATIONS

Size: Height: 2.4" (6.1 cm), Diameter: 4.0" (10.16 cm)
Shipping Weight: 4.6 ounces
Color: Ivory
Operating Humidity Range: 10 to 93% relative humidity

(non-condensing)
Application Temperature Range: 32°F to 100°F (0°C to

38°C)

ELECTRICAL SPECIFICATIONS

Operating Voltage Range: 15 to 32VDC
Maximum Standby Current: 200μA at 24VDC (no

communications)
Maximum Alarm Current (LED on): 7mA at 24VDC

SENSITIVITY SETTINGS & SUGGESTED APPLICATION

Level 1: 1% per foot (30.48 cm) of smoke. Very clean

environments - Laboratories.
Level 2: 2% per foot (30.48 cm) of smoke. Clean

environments - Offices.
Level 3: 3% per foot (30.48 cm) of smoke. Moderately clean

environments - Hotel Room, Dorm Room.
Level 4: 3% per foot (30.48 cm) of smoke with different

algorithm processing and weighting of sensor elements. Hotel

rooms near a shower, Boiler Rooms.
Level 5: 4% per foot (30.48 cm) of smoke. Equipment rooms,

Kitchens, Paint Shops.
Level 6: Thermal alarm at 135°F (57°C).

NOTE: Once the CO cell has reached the end of life, any device
set to Level 3 or Level 4 will default to Level 5 and Level 5 will drop
to 3%. The following sensitivities apply to devices with expired CO
cells:

Level 1: 1% per foot (30.48 cm) of smoke. Very clean

environments - Laboratories.
Level 2: 2% per foot (30.48 cm) of smoke. Clean

environments - Offices.
Level 5: 3% per foot (30.48 cm) of smoke. Moderately clean

environments - Hotel Room, Dorm Room.
Level 6: Thermal alarm at 135°F (57°C).

FSC-851 IntelliQuad

Advanced Multi-Criteria Detector

4.0"

(10.16 cm)

2.4"

(6.096 cm)

60412

dia

.wmf