Recommended coverage per detector, Installation, Agency listings and approvals – Notifier FSL-751 User Manual

Page 2: Product line information

Advertising
background image

Page 2 of 2 — DN-6886:C • 07/12/2012

NOTIFIER®, FlashScan®, and VIEW® are registered trademarks of

Honeywell International Inc.

FlashScan® and VIEW® are registered trademarks of Honeywell

International Inc.

©2012 by Honeywell International Inc. All rights reserved. Unauthorized use

of this document is strictly prohibited.

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.

www.notifier.com

Made in the U.S. A.

Recommended Coverage Per Detector

In order to support sophisticated smoke/dust discrimination

algorithms (cooperating multi-detector), it is recommended

that at least two FSL-751 detectors be installed in each room

or enclosed area.
Recommended coverage per detector is 400 square feet

(37.16 square meters).

Installation

The FSL-751 plug-in detector uses a separate base to simplify

installation, service, and maintenance. A special tool allows

maintenance personnel to plug in and remove detectors with-

out using a ladder.
Mount base on a box which is at least 1.5" (38.1 mm) deep.

Suitable mounting base boxes include:
• 4" (101.6 mm) square box.
• 3-1/2" (88.9 mm) or 4" (101.6 mm) octagonal box.
• Single-gang box (except relay or isolator base).

Agency Listings and Approvals

These listings and approvals apply to the modules specified in

this document. In some cases, certain modules or applications

may not be listed by certain approval agencies, or listing may

be in process. Consult factory for latest listing status.

UL Listed: S1115.

ULC Listed: S1115.

MEA Listed: 128-07-E (NFS2-640, NFS-320); 3-02-E.

FM Approved.

CSFM: 7272-0028:0218

BSMI: CI313066760036.

CCCF: Certif. # 2004081801000015.

When used with NFS2-640/NFS-320, MARINE-EQ, and

appropriate seismic bracket, these detectors are approved by

the following agencies:

U.S. Coast Guard: 161.002/50/0 (Standard 46 CFR).
Lloyd's Register: 11/600013 (ENV 3 category).

Product Line Information

NOTE: “A” suffix indicates ULC Listed model.

FSL-751(A): Laser Detector. Intelligent laser sensor with

FlashScan® capabilities. Mounts to one of the bases listed

below.

INTELLIGENT BASES

NOTE: “A” suffix indicates ULC Listed model.

NOTE: For details on intelligent bases, see DN-60054.

B210LP

(A)

: Standard U.S. flanged low-profile mounting base.

B210LPBP: Bulk pack of B210LP; package contains 10.
B501

(A)

: Standard European flangeless mounting base.

B501BP: Bulk pack of B501; package contains 10.
B200S

(A)

: Intelligent, programmable sounder base capable of

producing sound output in high or low volume with ANSI Tem-

poral 3, ANSI Temporal 4, continuous tone, marching tone,

and custom tone.
B200SR

(A)

: Intelligent sounder base capable of producing

sound output with ANSI Temporal 3 or continuous tone.

Replaces B501BH series bases in retrofit applications.
B224RB

(A)

: Plug-in System Sensor relay base. Screw termi-

nals: up to 14 AWG (2.0 mm²). Relay type: Form-C. Rating: 2.0

A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @

30 VDC inductive.
B224BI(A): Plug-in System Sensor isolator detector base.

Maximum 25 devices between isolator base.

ACCESSORIES

RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Mounts to

a U.S. single-gang electrical box. For use with B501(A) and

B210LP(A) bases only.
SMB600: Surface mounting kit.
M02-04-00:Test magnet.
M02-09-00: Test magnet with telescoping handle.
XR2B: Detector removal tool. Allows installation and/or

removal of detector heads from bases in high ceiling applica-

tions.
XP-4: Extension pole for XR2B. Comes in three 5-foot

(1.524 m) sections.
MOD400R: Detector sensitivity test tool. Use with most analog

or digital multimeters. Satisfies requirement of NFPA72 for

sensitivity testing.