Ndm-100(a) dual monitor module, Installation, Agency listings and approvals – Notifier NDM-100(P) User Manual

Page 3: Product line information

Advertising
background image

DN-6999:C • 10/06/2010 — Page 3 of 4

NDM-100(A) Dual Monitor Module

The NDM-100(A) Dual Monitor Module is intended for use in

intelligent, two-wire systems. It provides two independent two-

wire initiating device circuits (IDCs) at two separate, consecutive

addresses. It is capable of monitoring normally open contact fire

alarm and supervisory devices. The module has a single panel-

controlled LED.
NOTE: The NDM-100(A) provides two Style B (Class B) IDC cir-
cuits ONLY. Style D (Class A) IDC circuits are NOT supported in
any application.

NDM-100(A) SPECIFICATIONS

Normal operating voltage range: 15 to 32 VDC.
Maximum current draw: 6.4 mA (LED on).
Average operating current: 750 μA (LED flashing).
Maximum IDC wiring resistance: 1,500 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 240 μA
EOL resistance: 47K ohms.
Maximum SLC Wiring resistance: 40 Ohms.
Temperature range: 32° to 120°F (0° to 49°C).
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x

2.125" (5.398 cm) deep.

NDM-100(A) AUTOMATIC ADDRESSING

The NDM-100(A) automatically assigns itself to two address-

able points, starting with the original address. For example, if

the NDM-100(A) is set to address “26”, then it will automati-

cally assign itself to addresses “26” and “27”.

NOTE: “Ones” addresses on the NDM-100(A) are 0, 2, 4, 6, or 8
only. Terminals 6 and 7 use the first address, and terminals 8 and
9 use the second address.

Installation

NMM-100(A), NZM-100(A), and NDM-100(A) modules mount

directly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm)

deep, electrical box. They may also be mounted to the

SMB500 surface-mount box. Mounting hardware and installa-

tion instructions are provided with each module. All wiring

must conform to applicable local codes, ordinances, and regu-

lations. These modules are intended for power-limited wiring

only.
The NMM-100P(A) module is intended to be wired and

mounted without rigid connections inside a standard electrical

box. All wiring must conform to applicable local codes, ordi-

nances, and regulations.

Agency Listings and Approvals

In some cases, certain modules may not be listed by certain

approval agencies, or listing may be in process. Consult fac-

tory for latest listing status.

UL: S635

ULC: S635

• FM Approved

CSFM: 7300-0028:0230 (NMM-100, NMM-100P, NZM-

100); 7300-0028:0237 (NDM-100)

MEA: 72-01-E Vol. 2 (NMM-100, NMM-100P, NZM-100);

227-03-E Vol. 3 (NDM-100)

Product Line Information

NOTE: “A” suffix indicates ULC-listed model.

NMM-100(A): Monitor module.
NMM-100P(A): Monitor module, miniature.
NZM-100(A): Monitor module, two-wire detectors.
NDM-100(A): Monitor module, dual, two independent Class B

circuits.
SMB500: Optional surface-mount backbox.

NOTE: See installation instructions and refer to the SLC Wiring
Manual, PN 52304.

!

CAUTION:
Avoid duplicating addresses on the system.