Detector Sensitivity Test

Each detector can have its sensitivity tested (required per

NFPA 72, Chapter 14 on Inspection, Testing and Maintenance)

when installed/connected to a FireWarden-100-2 or FireWar-

den-50 addressable fire alarm control panel. The results of the

sensitivity test can be printed off the FireWarden-100-2 or Fire-

Warden-50 for record keeping.

Specification

Voltage range: 15 – 32 VDC (peak).
Standby current: 300 μA @ 24 VDC.
LED current: 6.5 mA @ 24 VDC (latched “ON”).
Air velocity: 4,000 ft./min. (20 m/sec.) maximum.
Size: 2.1" (5.33 cm) high; base determines diameter.

– B210LP(A): 6.1" (15.5 cm) diameter.
– B501(A): 4.1" (10.4 cm) diameter.
– B200SR(A): 6.875" (17.46 cm) diameter.
– B224RB(A): 6.2" (15.748 cm) diameter.

Weight: 3.6 oz. (102 g).
Operating temperature range: for NP-100(A): 0°C to 49°C

(32°F to 120°F); for NP-100T(A): 0°C to 38°C (32°F to 100°F).
NP-100R(A):

installed in a DNR(A)/DNRW -20°C to 70°C (-4°F

to 158°F).
Temperature: 0°C – 49°C (32°F – 120°F).
Relative humidity: 10% – 93%, non-condensing.

Listings

Listings and approvals below apply to the NP-100(A), NP-

100T(A), and NP-100R(A) detectors. In some cases, certain

modules may not be listed by certain approval agencies, or

listing may be in process. Consult factory for latest listing sta-

tus.

UL Listed: S1115.

ULC Listed: S911.

CSFM: 7272-0028:0231.

MEA: 243-02-E Vol. 2.

Maryland State Fire Marshal: permit 2173.

FM approved.

Product Line Information

NOTE: “A” suffix indicates ULC Listed model.

NP-100: Adressable photoelectric detector; B210LP base

included.
NP-100A: Sames as NP-100 with ULC Listing; B210LPA base

included.
NP-100T: Same as NP-100 but with thermal element;

B210LP base included.
NP-100TA: Same as NP-100T with ULC Listing; B210LPA

base included.
NP-100R: Remote test capable addressable photoelectric

detector for use with a DNRA/DNRW duct detector housing;

B210LP base included.

NP-100RA: Same as NP-100R with ULC Listing for use with a

DNRA duct detector housing; B210LPA base included.

INTELLIGENT BASES

NOTE: “A” suffix indicates ULC Listed model.

NOTE: For details about intelligent bases and their mounting, see
DN-60054.

B210LP

(A)

: Plug-in detector base (included); standard U.S.

flanged low-profile mounting base.
B210LPBP: Bulk pack of B210LP; package contains 10.
B501

(A)

: Standard European flangeless mounting base.

B501BP: Bulk pack of B501; package contains 10.
B200SR

(A)

: Intelligent sounder base capable of producing

sound output with ANSI Temporal 3 or continuous tone.

Replaces B501BH series bases in retrofit applications.
B224RB

(A)

: Plug-in System Sensor relay base. Screw termi-

nals: up to 14 AWG (2.0 mm²). Relay type: Form-C. Rating: 2.0

A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @

30 VDC inductive.
B224BI(A): Plug-in System Sensor isolator detector base.

Maximum 25 devices between isolator bases (see DN-6994).

ACCESSORIES

F110: Retrofit flange to convert B210LP(A) to match the

B710LP(A) profile, or to convert older high-profile bases to

low-profile.
F110BP: Bulk pack of F110; package contains 15.
F210: Replacement flange for B210LP(A) base.
RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Mounts to

a U.S. single-gang electrical box. For use with B501(A) and

B210LP(A) bases only.
SMB600: Surface mounting kit
M02-04-00:Test magnet.
M02-09-00: Test magnet with telescoping handle.
XR2B: Detector removal tool. Allows installation and/or

removal of detector heads from bases in high ceiling applica-

tions.
XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524

m) sections.
T55-127-010: Detector removal tool without pole.
BCK-200B: Black detector covers for use with NP-100(A) only;

box of 10.
WCK-200B: White detector covers for use with NP-100(A)

only; box of 10.