Cone of vision, Installation and wiring, Maintenance – Notifier 30-2021E-24 User Manual

Page 2: Engineering specifications, Agency listings and approvals

Advertising
background image

Page 2 of 4 — DN-1253:B • 8/25/2010

Cone of Vision

The Model 30-2021-24 has an 180° cone of vision. Relative

sensitivity is greatest at a viewing angle of 45° on either side of

the central axis. At angles greater than 45°, sensitivity

decreases, as illustrated in Figure 3. For the viewing pattern of

Model 30-2021E-24, with 60° cone of vision, see Figure 4.

Installation And Wiring

The Model 30-2021-24 and Model 30-2021E-24 are intended

for use in indoor applications. Connection to both models is via

color-coded wire leads with the following functions:

RED: +24 V operating power input.

BLACK: Common 24 V operating power input.

WHITE: ALARM relay – common.

BLUE: ALARM relay – normally closed contact.

ORANGE: ALARM relay – normally open contact.

The Model 30-2021-24 can be mounted on a standard 4"

(10.16 cm) junction box. The junction box should be mounted

securely to a supporting surface such as a wall, piping, etc.

See Figure 5 for 30-2021-24 mounting hole locations. Connect

the external wiring to the detector as illustrated in Figure 7 and
Figure 8

.

To install the Model 30-2021E-24, remove the front cover from

the detector and mount the detector on the junction box. See
Figure 6

for 30-2021E-24 mounting hole locations. Make the

electrical connections as shown in Figure 7 and Figure 8.

Place the cover back on the detector and mount it to any flat

surface.
A swivel mount is available for use with the Model 30-2021E to

facilitate installation and orientation and provide easy adjust-

ment for the viewing field of the detector — order part number

10-3995. This optional accessory meets the same NEC

requirements for use in hazardous areas as the detector.

Maintenance

To assure maximum detector sensitivity, keep the surface of

the sensor tube free from dirt or other contaminants at all

times. Periodically test the sensitivity of the detector using a

controlled flame or a UV test lamp such as the model W8066.

Engineering Specifications

The unit shall be an open area ultraviolet flame detector

designed to operate on 24 VDC.
It shall have encapsulated electronic circuitry and Form-C

alarm relay contacts. The unit shall have built-in alarm indica-

tion from the front of the detector. It shall respond to a 12-inch

(30.48 cm) diameter gasoline fire in six seconds when viewed

head-on from a distance of 30 feet (9.144 m). The detector

shall not respond to normal ambient light conditions such as

sunlight, incandescent, or fluorescent light.
The detector shall have a three-second time delay to spurious

responses. Model 30-2021-24 shall have a 180° cone of vision

with the greatest sensitivity at 45° on either side of the central

axis. Model 30-2021E-24 shall have a 60° cone of vision.
Explosion-proof units shall meet NEC Class I, Groups C and

D; Class II Groups E, F, and G; Class III.

Agency Listings and Approvals

Consult panel manuals for lists of compatible UL-Listed
devices. In some cases, certain modules or applications may
not be listed by certain approval agencies, or listing may be in
progress. Consult factory for latest listing status.

Figure 1 Model 30-2021-24 Detector Sensitivity

1253f1a.wmf

1253f1b.wmf

Figure 2 Model 30-2021E-24 Detector Sensitivity

1253f2a.wmf

1253f2b.wmf

Figure 3 Model 30-2021-24

1253fig3.wmf

Figure 4 Model 30-2021E-24

1253fig4.wmf