General specifi cations – Notifier FD Series Single UV User Manual

Page 3

Advertising
background image

General Specifi cations

Standard Specifications for “S” Series Ultraviolet Flame Detection

Operating Voltage Range

10 to 32 V

DC

Power Consumption

A Version:

Nominal 32 mA / 0.768 W | Maximum 64 mA / 1.54W

(at 24 V

DC

)

AR Version: Nominal 51 mA / 1.23 W | Maximum 82 mA / 1.97W

Temperature Range

Certified:

-40°C to +75°C (-40°F to +167°F)

Operational: -50°C to +75°C (-58°F to +167°F)

Field View

120° horizontal / 95° vertical

Spectral Range

UV Radiation 185 to 260 nanometres (1850 to 2600 angstroms)

Time Delay

DIP switch selectable to 3, 4, 5, 7 seconds

Sensitivity Settings

DIP switch selectable to 8, 16, 24 or 32 counts per second

Typical Response Time

<4 seconds depending on fuel source, fire size and distance

Enclosure Material

Yellow powdercoat with clear anodizing, copper-free aluminum (optional stainless steel), factory sealed housing

Humidity Range

0 to 95% RH, non-condensing

Weight (with swivel)

2.1 kg / 4.5 lb.

Stainless steel option: 3.4 kg / 7.5 lb.

Outputs

A Version:

0 to 20 mA - Into a maximum loop impedance of 800 Ohms at 32 V

DC

or 150 Ohms at 11.0 V

DC

Non-isolated loop supply

AR Version: Form C contacts rated 1 Amp at 30 V

DC

, 0.5 Amp at 125 V

AC

Selectable

energized/de-energized, latching/non-latching fire relay

Fault relay factory set as energized/non-latching, cannot be modified

Certifications

CSA - Class I, Division 1, Groups B, C and D - Temperature code T4 - CANADA: Class 1, Zone 1, Ex d IIB + H2 T4

ANSI/UL - Class I, Division 1, Groups B, C and D - Temperature code T4 - UNITED STATES: Class 1, Zone 1, AEx d IIB + H2 T5

NEMA Type 4X • IP67 - Enclosure ratings

Warranty

3 years for electronics

2 years for sensors

Standard Specifications for “U” Series Ultraviolet Flame Detection (Hydrogen)

Operating Voltage Range

10.5 to 32 V

DC

Power Consumption

A Version:

Nominal 80 mA / 1.92 W | Maximum 100 mA / 2.4W

(at 24 V

DC

)

AR Version: Nominal 100 mA / 2.4 W | Maximum 120 mA / 2.9W

Temperature Range

Certified:

-40°C to +85°C (-40°F to +185°F)

Operational: -55°C to +125°C (-65°F to +257°F)

Field View

120° horizontal / 95° vertical

Spectral Range

UV Radiation 185 to 260 nanometres (1850 to 2600 angstroms)

Time Delay

DIP switch selectable to 3, 4, 5, 7 seconds

Sensitivity Settings

DIP switch selectable to 8, 16, 24 or 32 counts per second

Typical Response Time

<4 seconds depending on fuel source, fire size and distance

Enclosure Material

Yellow powdercoat with clear anodizing, copper-free aluminum (optional stainless steel), factory sealed housing

Humidity Range

0 to 95% RH, non-condensing

Weight (with swivel)

2.1 kg / 4.5 lb.

Stainless steel option: 3.4 kg / 7.5 lb.

Outputs

A Version:

0 to 20 mA - Into a maximum loop impedance of 800 Ohms at 32 V

DC

or 150 Ohms at 11.0 V

DC

Non-isolated loop supply

AR Version: Form C contacts rated 1 Amp at 30 V

DC

, 0.5 Amp at 125 V

AC

Selectable

energized/de-energized, latching/non-latching Fire relay

Fault relay factory set as energized/non-latching, cannot be modified

Certifications

CSA - Class I, Division 1, Groups B, C and D - Temperature code T4 - CANADA: Class 1, Zone 1, Ex d IIB + H2 T4

ANSI/UL - Class I, Division 1, Groups B, C and D - Temperature code T4 - UNITED STATES: Class 1, Zone 1, AEx d IIB + H2 T5

NEMA Type 4X • IP67 - Enclosure ratings

Warranty

3 years for electronics

2 years for sensors

FD Series Single UV.indd 3